Do current transformers need recalibration after compensation?

Jan 30, 2026|

I. Why is recalibration necessary?

1. Compensation changes parameters:

Turnings compensation adjusts the number of turns in the secondary winding, directly affecting the turns ratio and error.

Capacitor compensation changes the secondary impedance, leading to a change in phase difference.

Magnetic shunt compensation adjusts the magnetic circuit structure, affecting magnetic flux distribution.

2. Error may exceed limits again:

If not calibrated after compensation, the error may exceed the accuracy class limit (e.g., the ratio difference of a 0.5 class transformer should be within ±0.5%).

II. Key calibration steps:

1. Preparation stage:

Demagnetize the transformer under test and check the wiring.

Apply a sinusoidal current at rated frequency, and connect the specified load to the secondary side.

2. Testing stage:

Read the ratio difference and phase difference using a calibrator.

Record the data and compare it with the accuracy class limit.

3. Verification stage:

The error after compensation must return to within the limit.

Protective current transformers must be ensured not to affect protection operation.

III. Precautions

Environmental Control: Temperature, humidity, and electromagnetic interference can affect results.

Wiring Specifications: Ensure correct polarity and avoid short circuits.

Instrument Selection: A 0.05S-level error tester is recommended, supporting ratio and polarity detection.