Do current transformers need recalibration after compensation?
Jan 30, 2026| I. Why is recalibration necessary?
1. Compensation changes parameters:
Turnings compensation adjusts the number of turns in the secondary winding, directly affecting the turns ratio and error.
Capacitor compensation changes the secondary impedance, leading to a change in phase difference.
Magnetic shunt compensation adjusts the magnetic circuit structure, affecting magnetic flux distribution.
2. Error may exceed limits again:
If not calibrated after compensation, the error may exceed the accuracy class limit (e.g., the ratio difference of a 0.5 class transformer should be within ±0.5%).
II. Key calibration steps:
1. Preparation stage:
Demagnetize the transformer under test and check the wiring.
Apply a sinusoidal current at rated frequency, and connect the specified load to the secondary side.
2. Testing stage:
Read the ratio difference and phase difference using a calibrator.
Record the data and compare it with the accuracy class limit.
3. Verification stage:
The error after compensation must return to within the limit.
Protective current transformers must be ensured not to affect protection operation.
III. Precautions
Environmental Control: Temperature, humidity, and electromagnetic interference can affect results.
Wiring Specifications: Ensure correct polarity and avoid short circuits.
Instrument Selection: A 0.05S-level error tester is recommended, supporting ratio and polarity detection.