How to identify the current transformer is good or bad?

Jul 05, 2023|

First answer

For high-voltage current transformers: the secondary circuit of the current transformer can only have a small impedance, so it tends to be short-circuited during normal operation, and the sound is very small, but the sound is louder during faults. The grounding should be good, and the lead-out line of the primary winding of the capacitive current transformer should be reliably grounded. There should be no oil leakage in the oil-immersed transformer. In addition, when the secondary winding or circuit of the current transformer is short-circuited, the ammeter and power meter indicate zero; when the secondary circuit of the current transformer is open, the terminal at the fault point will break down and ignite.


Take the following measurements:
1. The insulation resistance of the winding;

2. Medium loss; the measured value should meet the relevant regulations


second answer

1. Appearance: Whether the current transformer shell, insulation, coil, etc. have signs of aging, electric shock, burnt, etc. The following refers to the current transformer below 500V, check with a 500V megohmmeter.

2, The primary coil is connected and cannot be broken.

3. The secondary coil is connected and cannot be broken.

4. The primary coil and the secondary coil cannot be connected.

5. Use a 500V megohmmeter to check the insulation resistance. The insulation between the primary coil and the secondary coil is greater than 0.38 megohm.

6. Use a current clamp meter to monitor whether the current ratio is correct. (mainly to check whether there is a partial short circuit between the turns inside the coil).