How to prevent the current transformer from saturation?
Mar 19, 2025| 1. Reasonably select the transformation ratio of the current transformer
Select the transformation ratio according to the actual load current
When selecting a current transformer, the appropriate transformation ratio should be selected according to the maximum operating current of the circuit under test so that the primary current does not exceed the rated current of the current transformer within the normal operating range.
For example, if the maximum current of the circuit under test is 600A, a current transformer with a transformation ratio of 600/5 or higher (such as 800/5) can be selected.
The appropriate transformation ratio ensures that the core will not saturate under normal operating current, thereby ensuring measurement accuracy and reliability of the protection device.
Consider future system expansion
When selecting the transformation ratio of the current transformer, the possible future expansion or load increase of the system should be considered. Selecting a slightly larger transformation ratio can provide margin for future system expansion.
2. Ensure that the secondary side is closed
Avoid opening the secondary side
The secondary side of the current transformer must always be closed and cannot be open. If the secondary side is open, the primary current will be used entirely for excitation, causing the core to saturate quickly.
During installation and maintenance, ensure that the secondary circuit is connected reliably to avoid loose or broken wiring.
Connect the secondary load correctly
The secondary load should meet the rated load requirements of the current transformer. Excessive load impedance may cause the secondary current to drop, affecting the measurement accuracy; too small load impedance may cause the core magnetic flux density to increase, increasing the risk of saturation.
3. Use anti-saturation current transformer
Electronic current transformer
Electronic current transformers (such as optical current transformers and air-core coil current transformers) have anti-saturation characteristics. They are not affected by core saturation and can maintain a stable output signal under high current.
Electronic current transformers also have the advantages of high precision and strong anti-interference ability, and are suitable for occasions with high requirements for measurement accuracy and reliability.
High saturation flux density core
Some current transformers use core materials with high saturation flux density, which can maintain good magnetic properties at higher flux density, thereby reducing saturation.
4. Regular maintenance and inspection
Excitation characteristic test
Perform excitation characteristic test on current transformer regularly. By measuring the relationship between excitation current and magnetic flux density, it can be judged whether the core is close to saturation.
If the excitation current is found to increase sharply, it indicates that the core may be saturated, and measures should be taken in time.
Check the residual magnetism of the core
The residual magnetism in the core may affect the performance of the current transformer. Check the residual magnetism of the core regularly and demagnetize it when necessary.
Check the secondary circuit
Check the connection of the secondary circuit regularly to ensure that there is no looseness, broken wire or short circuit.
5. Other preventive measures
Limit the primary current
In system design, it is necessary to avoid the current transformer primary current exceeding the rated value for a long time. The overcurrent protection device can be used to cut off the excessive current in time.
Use appropriate protection device
Select appropriate protection device, such as differential protection device, and set it according to the characteristics of the current transformer.
Avoid overheating of the core
Overheating of the core may cause the magnetic properties to decrease and increase the risk of saturation. Ensure that the heat dissipation of the current transformer is good to avoid long-term overload operation.