How to reduce the leakage reactance of the current transformer?

Jan 17, 2025|

1. Winding structure optimization
Reasonable winding arrangement
Layered winding: Layered winding can effectively reduce leakage reactance. The primary winding and the secondary winding are wound alternately in layers, for example, one layer of primary winding and one layer of secondary winding. This can make the magnetic coupling between the primary winding and the secondary winding closer and reduce the leakage flux. Because the magnetic field interaction between adjacent winding layers is enhanced, the magnetic flux can pass through the two windings more, thereby reducing the generation of leakage flux and reducing the leakage reactance.
Concentric winding and shortening the spacing: For concentrically wound current transformers, the spacing between the primary winding and the secondary winding should be shortened as much as possible. Reducing the spacing can increase the mutual inductance between the two windings, reduce the magnetic resistance of the leakage flux path, enable more magnetic flux to couple between the two windings, and reduce the leakage reactance. At the same time, it is necessary to ensure the uniform distribution of the windings to avoid the increase of leakage flux caused by local magnetic field concentration.
Reduce the axial length of the winding
Compact design: Under the premise of meeting the insulation requirements and transformer performance, the axial length of the winding should be reduced as much as possible. A shorter axial length means that the path of the leakage flux is shorter. According to Ohm's law of magnetic circuit, the magnetic resistance is proportional to the length of the magnetic circuit, so the magnetic resistance decreases and the leakage flux will also decrease accordingly, thereby reducing the leakage reactance. This can be achieved by optimizing the overall structural design of the transformer, such as using thinner insulation materials, compact core shapes, etc.
2. Coordination of core shape and material selection
Core shape optimization
Application of toroidal core: The magnetic circuit of the toroidal core is closed, which can provide a uniform magnetic field environment for the winding. When the winding is wound on the toroidal core, the magnetic field can be better concentrated inside the core, reducing the leakage flux. Compared with other shapes of cores, the toroidal core can effectively reduce the leakage reactance. Moreover, the toroidal core can make the winding evenly distributed on the circumference, further enhancing the magnetic coupling between the windings, which helps to reduce the leakage reactance.
Core window size design: It is also important to reasonably design the core window size. The window size should be optimized according to the number of turns and wire diameter of the winding to ensure that the winding can be tightly wound on the core and reduce the gap between the winding and the core. Smaller gaps can reduce the generation of leakage flux, thereby reducing leakage reactance.
Consideration of the magnetic permeability of the core material: Selecting a core material with high magnetic permeability can indirectly reduce leakage reactance. High magnetic permeability materials can make the magnetic flux density in the core more easily reach saturation, thereby guiding more magnetic flux to pass through the core and reducing leakage flux. For example, materials such as Permalloy have high magnetic permeability. Using this material as the core can enhance the restraint ability of the magnetic field to a certain extent and reduce leakage reactance.
3. Adoption of shielding measures
Setting up an electromagnetic shielding layer
Winding shielding: Setting up an electromagnetic shielding layer around the winding is an effective way to reduce leakage reactance. A shielding layer can be made of a high magnetic permeability metal material (such as Permalloy foil or soft iron foil) to wrap the winding. The shielding layer can guide the leakage flux to form a closed loop inside the shielding layer, reducing the chance of leakage flux leaking outward, thereby reducing leakage reactance. At the same time, the shielding layer can also reduce the interference of the external electromagnetic field on the internal winding of the transformer.
Core shielding (if necessary): In some special cases, in order to further reduce leakage flux, the core can also be shielded. For example, when the transformer works in a strong electromagnetic interference environment or has extremely high precision requirements, a layer of shielding material can be set outside the core. This layer of shielding material can prevent the magnetic flux generated by the core from leaking to the external space, and can also block the interference of the external magnetic field on the core, thereby indirectly reducing the leakage reactance.

Send Inquiry