During operation, the secondary circuit of the Power Current Transformer may be opened by the terminal screws due to vibration, etc., causing the secondary circuit to open.

If the Power Current Transformer for the instrument is open, the open-circuit phase ammeter indicates zero, the speed of the electric energy meter drops, and the indications of the active and reactive power meters decrease;

If the Power Current Transformer for protection is open circuit, the zero sequence, negative sequence and differential protection may malfunction. program protection to exit operation.

If it is an external open circuit of the Power Current Transformer, safety measures should be taken. The operating personnel on duty should wear insulating shoes and gloves, first short-circuit the secondary side of the secondary side, then deal with the broken or loose wire, and then remove the grounding short-circuit wire to restore normal operation; if it is an internal open circuit, then The power failure should be dealt with. During the open circuit operation of the Power Current Transformer, the primary current should be appropriately reduced and the protection class should be notified in time for processing.

If the Power Current Transformer is too hot, there is discharge sound inside, serious oil leakage, etc., it needs to be powered off immediately.

During operation, if smoke or fire is found inside the Power Current Transformer, a circuit breaker should be used to cut it off, and a fire extinguisher such as carbon dioxide should be used to put out the fire.