The composition and working characteristics of current transformer

Sep 13, 2023|

1. The number of primary turns is small and the number of secondary turns is large.

For current transformers used in power systems, the primary winding is usually the incoming and outgoing wires of the primary equipment, with only 1 or 2 turns; the number of secondary turns is large.

2. The working magnetic density in the iron core is very low, and the magnetic density is high when the system fails.

During normal operation, the operating magnetic density in the core of the current transformer is very low, and its primary and secondary phases maintain ampere-turn balance. When the system fails, due to the large fault current and high secondary voltage, the excitation current increases and the magnetic density in the iron core increases sharply, even saturating the iron core.

3. High internal resistance, current source

Under normal operating conditions, the magnetic density in the iron core is very low, the excitation impedance is large, and the number of secondary turns is large. Looking from the secondary side, its impedance is very large. Compared with the internal resistance of the current transformer, the load impedance is negligible, so the change of the load impedance has little effect on the secondary current, so it can be called a current source.

4. Small secondary load required

If the secondary load of the current transformer is large, its secondary voltage will be very high during operation, and the excitation current will inevitably increase, thereby increasing the current conversion error.

5. The secondary circuit must not be opened

If the secondary circuit is open during operation, the secondary current disappears, and the demagnetization effect also disappears, and the magnetic density in the iron core is very high; and because of the large number of secondary turns, the secondary voltage will be very high, sometimes up to Thousands of volts, endangering secondary equipment and personal safety.

Send Inquiry