The wiring principle of current transformer
Dec 14, 2022| 1. The secondary side of the current transformer is not allowed to open. The secondary open circuit may have serious consequences. One is that the iron core is overheated, and even the transformer is burned; the other is that due to the large number of turns of the secondary winding, a dangerous high voltage will be induced, endangering the safety of people and equipment.
2. The secondary side of the high-voltage current transformer must be grounded at one point. Since the primary side of the high voltage current transformer is high voltage, when the high voltage breakdown between the primary and secondary coils due to insulation damage, the high voltage will enter the low voltage. If the secondary coil is grounded at one point, the high voltage will be introduced into the ground, which can ensure Personal and equipment safety. But it should be noted that the secondary circuit of the current transformer is only allowed to be grounded at one point, and no more grounding is allowed, otherwise it may cause shunting and affect the use.
The secondary coil of the low-voltage current transformer should not be grounded. Due to the low voltage of the low-voltage transformer, the degree of insulation between the primary and secondary coils is large, and the possibility of breakdown of the primary and secondary coils is small. In addition, the ungrounded secondary coil will cause the secondary return.
The insulation capacity of the road and the instrument is improved, and the accident of the instrument being burned by the lightning strike can also be reduced. In addition, the differential protection is composed of differential relays. The current transformers on both sides of the differential protection can only be grounded at one point. Generally, the grounding point is set at the protection screen. When the differential protection adopts a microcomputer protection device, the two sides are connected. The current transformers should be grounded separately.
3. The measurement level and protection level of the current transformer cannot be wrongly connected. Due to the different thicknesses of the measurement and protection winding core designs, if the connection is wrong, first, the accuracy of the measurement during normal operation will be reduced, and the electric energy measurement will be inaccurate;
Second, when a short-circuit fault occurs, the design of the iron core of the metering winding ensures that the iron core is saturated when the short-circuit current exceeds a certain multiple of the rated current, which limits the growth of the secondary current to protect the meter. The core of the relay protection winding is not saturated, and the secondary current increases accordingly with the short-circuit current, so that the relay protection can act accurately. If the connection is wrong, the relay protection action is not sensitive, and the measuring instrument may burn out.
4. Since the secondary winding of the current transformer cannot be opened, the windings that are not used by the current transformer need to be short-circuited. However, for a current transformer with multiple taps, the unused taps should be empty and cannot be short-circuited. For example, a current transformer has secondary taps 1S1, 1S2, and 1S3, of which 1S1 and 1S2 are 300/5A, and 1S1 and 1S3 are 600. /5A, when you need to use 300/5A, connect 1S1 and 1S2 for use, and should not short-circuit 1S1 and 1S3, otherwise it will affect the measurement accuracy of the tap.
5. When wiring the metering winding of the current transformer and the relay protection winding that involves the direction, master two points to determine the wiring. One is to look at the installation position of the current transformer, that is, to determine which side of the L1 of the current transformer is installed; Depending on the winding function or the type of relay protection, the above two points can determine the secondary wiring of the current transformer.