Things to pay attention to when using Electrical Current Transformer

Apr 23, 2021|

(1) The iron core of the Electrical Current Transformer and the K2 (S2) end of the secondary winding must be reliably grounded. To protect test personnel and test equipment from accidental injury caused by insulation damage and leakage.


(2) During power-on use, the secondary circuit of the Electrical Current Transformer must not be opened. Because when the primary winding has current, if the secondary circuit is suddenly disconnected, it will cause the iron core of the transformer to be over-magnetized, causing the iron core to heat up, and in severe cases, the winding will be burned; at the same time, the secondary circuit will induce a high The electromotive force (which may reach several hundred volts) may endanger the safety of the operator or cause a short circuit between the turns of the transformer. For this reason, in practical circuits, the following measures are usually taken.

① Fuse should not be installed in the secondary circuit of Electrical Current Transformer.

②Use a switch and ammeter to connect in parallel, open the switch when reading the ammeter, and close the switch when necessary. For AC motor current measurement, setting this switch has another bigger purpose, which is when the motor is powered on. , Close the switch to allow most of the larger starting current to pass through the switch, so as to prevent the ammeter from being damaged by the larger current. This is the so-called "closed meter", and this kind of switch is also called "closed". Meter switch" or "sealed transformer secondary switch (referred to as sealed secondary switch)".

③For multi-rate transformers, when the ratio number needs to be replaced in the power-on test measurement, the operation should be carried out according to the principle of first closing the pre-replacement ratio switch and then disconnecting the original ratio switch, that is, "close first "After the break" principle.


Send Inquiry