What are some methods to dry current transformers?
Jul 10, 2026| What are some methods for drying current transformers?
I. Simple On-Site Drying (Slight/Moderate Moisture, No Factory Return Required)
Suitable for on-site drying of small and medium-sized current transformers, low cost and easy operation:
1. Hot Air Circulation Drying Method: Disassemble the junction box and base ventilation holes, circulate clean, dry hot air at 100~120℃ into the transformer body, and continue drying for 24~48 hours. Re-measure the insulation resistance every 6 hours. Stop drying after three consecutive stable insulation readings. Suitable for dry-type and oil-immersed transformers with slight moisture.
2. Short-Circuit Current Drying Method: Short-circuit the secondary winding, apply a small current to the primary side for heating, controlling the winding temperature to not exceed 85℃, and continue drying until the insulation resistance stabilizes and meets the standard. Suitable for low-voltage small and medium-sized current transformers with windings, and can be operated without disassembling the equipment. 3. Infrared Heating Drying Method: Infrared heating lamps are used to evenly heat the transformer body, controlling the surface temperature to not exceed 90℃. Combined with ventilation to remove moisture, this method is suitable for small-volume transformers mounted on outdoor poles or inside switch cabinets. It does not require power outages for disassembly and can be used for emergency treatment of condensation and moisture.
II. Professional Overall Drying (Severe Moisture, Deep Dehumidification): Suitable for severely damp or oil-immersed transformers, providing a more thorough treatment:
1. Vacuum Drying Method: The transformer is placed in a vacuum chamber, and a vacuum is created to lower the boiling point of water. Drying nitrogen gas at 100~110℃ is circulated and heated continuously for 24~36 hours. This method deeply removes moisture from the insulation, providing better results than ordinary hot air drying. It is the preferred method for severely damp epoxy dry-type transformers.
2. Dedicated Drying Treatment for Oil-Immersed Instrument Transformers: First, drain the old insulating oil. Vacuum heat the transformer body to 100-105℃ and maintain this temperature for 24 hours to remove moisture from the insulating paper. Then, perform vacuum dehydration and degassing regeneration on the old insulating oil. After passing inspection, re-inject it into the transformer. Finally, replace all sealing strips and reseal the transformer to completely solve the moisture problem.
3. Induction Heating Vacuum Drying Method: Apply a power frequency induced current to the primary winding to heat the core and windings. Combined with vacuuming to remove moisture, this method provides uniform heating and easily controllable temperature. It is suitable for large-capacity high-voltage instrument transformers and can prevent insulation overheating and aging.