What factors will affect the measurement accuracy of the current transformer?
Oct 04, 2024| 1. Internal parameters:
1. Secondary coil internal resistance and leakage reactance: When the secondary coil internal resistance increases, the ratio difference and angle difference increase; when the leakage reactance increases, the ratio difference increases, but the angle difference decreases. However, the secondary coil internal resistance and leakage reactance are usually smaller than the secondary load, so their changes generally have little effect on the error, but the impact on small-capacity current transformers is more significant.
2. Core cross section: Increasing the core cross section will reduce the core magnetic flux density and reduce the excitation current, thereby increasing the ratio difference and angle difference. However, for unbalanced current transformers, the magnetic flux density is small under rated conditions, and reducing the magnetic flux density may not reduce the excitation current much. The magnetic flux density is smaller and the error difference is not obvious.
3. Number of turns: Increasing the number of coil turns can increase the number of ampere-turns, reduce the magnetic flux density, and improve the error more significantly than increasing the core cross section. However, increasing the number of coil turns will increase the amount of copper, reduce the dynamic stability coefficient, and increase the saturation coefficient. For single-turn current transformers (such as through-core or bushing current transformers, which only allow one turn), the error cannot be improved by increasing the number of turns.
4. Iron loss and magnetic permeability: When the core flux density remains unchanged, reducing the core excitation ampere and loss ampere can improve the ratio error and angle error. Therefore, the magnetic permeability can be improved and the iron loss can be reduced by using high-quality magnetic materials and adopting appropriate annealing processes, but the strength of the core will also affect the saturation coefficient. When the magnetic properties are poor, the saturation coefficient of the core is small.
2. Operating conditions:
1. Current frequency change: The effect of current frequency change on the error is more complicated. Generally speaking, the effect of system frequency change is negligible when the system frequency changes very little; but if the frequency changes too much, for example, using a current transformer with a rated frequency of 50Hz in a 60Hz system, the effect of frequency needs to be considered, because frequency changes not only affect core loss, magnetic flux density and coil leakage reactance, but also affect the value of secondary load reactance.
2. Primary current size: When the primary current decreases, the magnetic flux density decreases proportionally, but at low magnetic flux density, the decrease in excitation ampere is slower than the decrease in magnetic flux density, so the absolute value of the difference and the angular difference increase relatively.
3. Secondary load: When the secondary load impedance changes within the specified range, the secondary current size is not affected. Therefore, when the secondary load is reduced to the rated range, the magnetic flux density will also decrease. Since the secondary current is constant, the excitation current decreases and the error also decreases. The factory manual of the current transformer generally indicates the rated secondary load impedance value. During operation, the error should be checked according to the maximum secondary load impedance value under the given wiring method. It should be noted that if the secondary load exceeds the rated load, it will cause the transformer core to be magnetically saturated, thereby increasing the error.
4. Power factor of the load: The power factor of the secondary load increases, that is, the resistance increases, the reactance decreases, the angular difference increases, and the ratio decreases. For the saturation factor, the saturation factor indicated in the transformer manufacturer's manual refers to the saturation factor when the power factor is 0.8. This value is equivalent to the "minimum value" of the saturation factor, so the saturation factor will increase when the power factor increases or decreases.
3. External environment:
1. Temperature influence: The temperature change of the operating environment will affect the magnetic material performance of the transformer. When the temperature is too high or too low, it may cause thermal drift or cold drift of the transformer, resulting in an increase in measurement error. For example, high temperature may reduce the magnetic permeability of the core, and low temperature may increase the resistance of the winding, thereby affecting the measurement accuracy of the transformer.
2. Humidity influence: Although the measurement accuracy of the transformer is relatively less affected by humidity, excessively high or low humidity may also have a certain impact on it, such as causing insulation performance degradation, rusting of the core, and other problems, which indirectly affect the measurement accuracy.
3. Electromagnetic interference: In some occasions with complex electromagnetic environments, such as strong electromagnetic field sources nearby or harmonic interference in the power system, it may affect the measurement of the current transformer, resulting in an increase in measurement error.
4. Other factors:
1. Residual magnetism: The current transformer may generate residual magnetism after experiencing a large current, and the presence of residual magnetism will affect the measurement accuracy of the transformer.
2. Polarity error: It is very important to ensure that the polarity of the current transformer is connected correctly. Polarity error may cause serious errors in the measurement results and even cause the protection device to malfunction. When wiring, the primary and secondary windings should be correctly connected according to the transformer's markings and relevant standards.
3. Improper installation and use: For example, the installation position of the current transformer does not meet the requirements and is affected by external mechanical forces; or during use, abnormal conditions such as open circuit and short circuit on the secondary side will affect its measurement accuracy and may even damage the transformer.
4. The quality and performance of the transformer itself: The quality and performance of current transformers produced by different manufacturers may vary, which will also affect the measurement accuracy. For example, differences in the material of the core, the manufacturing process, the winding quality of the winding, etc. may all lead to different errors in the transformer.