What problems should be paid attention to in daily use of Electrical Current Transformer
Nov 09, 2021| One, the electrical current transformer polarity connection must be correct
Electrical Current Transformer generally reduces the polarity marking. If the polarity is not connected correctly, it will affect the measurement, and even when there are multiple current mutual inductances on the same line in parallel, all of them will cause a short circuit accident.
Second, the secondary circuit of the Electrical Current Transformer should have a protective grounding point
In order to prevent the high voltage from entering the low-voltage side after the insulation breakdown between the primary and secondary windings and endangering the safety of people and instruments, the secondary side of the Electrical Current Transformer should be equipped with a protective grounding point. Only one grounding point is allowed to be connected. Generally, it will be close to the Electrical Current. The box terminal of Transformer is grounded.
Three, the secondary winding is not allowed to be open during operation
Otherwise, it will lead to the following serious consequences: high voltage on the secondary side, endangering the safety of personnel and instruments; overheating, may burn out the windings; increase the measurement error.
Four, about the relay protection device
The secondary circuit of the Electrical Current Transformer used for electric energy measurement should not be connected to relay protection devices and automatic devices to prevent mutual influence.