How to check the sealing of the current transformer?
Feb 07, 2025| 1. Appearance inspection
Sealing gasket inspection: Carefully check the sealing gasket of the current transformer housing. The sealing gasket is usually located at the connection between the cover and the housing of the transformer, around the inlet and outlet terminals, etc. Check whether the gasket shows signs of aging, deformation, damage or falling off. For example, if the rubber sealing gasket cracks, hardens or loses elasticity, it may cause a poor seal. For an aged gasket, its color may become darker or the surface may become powdery.
Inspection of the housing connection: Check whether the connection of the transformer housing is tight. Observe the joints of the housing to see if there are gaps or misalignment. For parts connected by bolts, check whether the bolts are loose. If the bolts are loose, gaps may be created between the housings, thereby destroying the sealing effect. At the same time, check whether there are signs of leakage such as oil stains and water stains at the connection parts, which may indicate a problem with the seal.
Inlet and outlet terminal inspection: The sealing at the inlet and outlet terminals is very important to prevent moisture and impurities from entering the transformer. Check whether the sealing sleeve of the terminal is intact and whether it is cracked or loose. If the sealing sleeve is damaged, moisture may enter the transformer along the wire and affect the insulation performance.
2. Pressure test (applicable to some current transformers with pressure requirements)
Principle and method: For some current transformers with internal pressure requirements (such as SF6 gas insulated current transformers), the sealing condition can be checked by pressure test. Use professional pressure detection equipment to monitor the internal pressure of the transformer when it is operating normally. If the pressure drops more than the specified rate or is lower than the specified lower limit, it may indicate that there is a leak and there is a problem with the seal. For example, record the pressure value inside the transformer in the initial stage, measure it again after a period of time (such as one week, one month, etc.), and calculate the pressure change rate.
Precautions: When performing pressure testing, ensure the accuracy and reliability of the test equipment. At the same time, operate according to the technical parameters of the transformer and the pressure range specified by the manufacturer. Because too high pressure may cause damage to the transformer, too low pressure may not accurately detect the sealing problem. In addition, for oil-filled current transformers, although pressure testing is generally not performed, the oil level gauge can be observed. If the oil level drops abnormally, it may be due to poor sealing and oil leakage.
3. Leak test (applicable to oil-immersed and gas-insulated current transformers)
Gas leak detection (taking SF6 gas as an example): For SF6 gas-insulated current transformers, gas leak detectors can be used for detection. Common leak detection methods include qualitative leak detection and quantitative leak detection. Qualitative leak detection uses a leak detector to detect whether there is SF6 gas leakage around the transformer. When the leak detector sounds an alarm, it indicates that there may be a leak point. Quantitative leak detection can accurately measure the amount of leaked gas, generally using the hanging bottle method or local bandaging method. The hanging bottle method is to hang a bottle of known volume upside down on the suspected leaking part, and after a certain period of time, measure the amount of gas collected in the bottle; the local bandaging method is to wrap the suspected leaking part with airtight materials, and after a period of time, detect the gas concentration inside the bandage and calculate the leakage.
Leak detection of oil-immersed current transformer: For oil-immersed current transformers, the sealing condition can be judged by checking whether there is oil leakage. Place clean white filter paper at the bottom of the transformer, the seam of the shell, etc. If you find oil stains on the paper, it means there is oil leakage. In addition, you can also check the oil level gauge to judge. If the oil level continues to drop and normal loss (such as oil level changes caused by oil temperature changes) is excluded, it may be caused by poor sealing.