How to identify the quality of current transformer?
Oct 30, 2023| First answer
For high-voltage current transformers: The secondary circuit of the current transformer can only carry a small impedance, so it tends to be in a short-circuit state during normal operation and the sound is very small, but the sound is loud during a fault. The grounding should be good, and the terminal lead of the primary winding of the capacitive current transformer should be reliably grounded. There should be no oil leakage from oil-immersed transformers. In addition, when the secondary winding or loop of the current transformer is short-circuited, the ammeter and power meter indicate zero; when the secondary loop of the current transformer is open-circuited, the fault point terminal will break down and catch fire.
Make the following measurements:
1. Insulation resistance of winding;
2. Media loss; measured values should comply with relevant regulations
Second answer
1. Appearance: Check whether the current transformer shell, insulation, coil, etc. have signs of aging, electric shock, scorching, etc. The following refers to current transformers below 500V, check with a 500V megger.
2. The primary coil path cannot be opened.
3. The secondary coil path cannot be opened.
4. The primary coil and secondary coil cannot communicate.
5. Use a 500V megger to check the insulation resistance. The insulation between the primary coil and the secondary coil and the shell is greater than 0.38 megohm.
6. Use a current clamp meter to monitor whether the current ratio is correct (mainly to check whether there is a local short circuit between the turns inside the coil).