How to install the current transformer
Jun 05, 2023| 1. Construct according to the drawing, the line wiring is accurate, the number marks at both ends are clear, and the label range meets the specified requirements.
2. The conductors or cables of the secondary circuit are made of copper wires, the conductor cross section of the current transformer circuit is not less than 2.5 square millimeters, and the conductor cross section of the voltage transformer circuit is not less than 1.5 square millimeters.
3. The first end of the current transformer outlet should choose a dedicated current terminal, and the secondary winding not used by the current transformer should be short-circuited and grounded on the wiring board.
4. There should be no seams in the box conductors of the secondary circuit, and there should be no joints between control cables or cables. If joints are required, terminal boxes for transition connections shall be used.
5. The polarity of the current transformer cannot be reversed or the phase sequence. Various designs and procedures are available. When the transformer uses differential protection, the current phasor diagram of the two arms must be measured before it can be put into operation to confirm whether the connection is correct.
6. The layout of the secondary circuit wires should be neat and beautiful. The connecting screws of the wires and electrical components and terminal blocks must not have false connections or loose connections, and the distance between the pinch points of the wires should meet the regulations.