How to operate the secondary side grounding of a current transformer?

Feb 25, 2026|

I. Core Operating Principles: Single-point grounding only

Single-point grounding is mandatory: The secondary circuit of a current transformer must have only one grounding point to avoid forming a closed loop and generating circulating current, which could lead to measurement errors or malfunctions in protection systems.

Multiple-point grounding is prohibited: If grounding is performed simultaneously in the terminal box and protection panel, ground circulating current will be generated due to potential differences, affecting the normal judgment of differential protection and other devices.

Uniqueness of grounding point: Regardless of the number of current transformers in the system, as long as there is an electrical connection in the secondary circuit (such as differential protection), they must be grounded at a unified point.

II. Selection of Grounding Point Location
Based on the type of current transformer and system configuration, the grounding point should be set according to the following rules:

Independent current transformers or circuits without electrical connection: Should be grounded at a single point in the terminal box of the switchyard to shorten the grounding path and improve high-voltage discharge efficiency.

Multiple related current transformers (such as bus differential protection): The grounding point should be located outside the terminal block in the relevant protection panel or control cabinet to achieve centralized grounding and avoid ground potential interference. High-voltage systems (10kV and above) must be forcibly grounded, with S2 or K2 terminals preferred as the grounding point.

Low-voltage systems (380V/220V) do not require grounding due to their large insulation margin; however, if grounded, the single-point principle must still be followed.

Analysis of Current Transformer Secondary Side Grounding Specifications
III. Specific Operating Steps

Confirm Terminal Polarity: Verify S1 (same-name terminal) and S2 (different-name terminal) to ensure S2 is the recommended grounding terminal. Incorrectly grounding S1 may result in ineffective high-voltage release during open circuit conditions.

Select a Suitable Grounding Wire: Use a yellow-green bicolor copper core flexible wire with a cross-section of not less than 4mm² to ensure conductivity and mechanical strength.

Connect to the Designated Grounding Point: Securely connect one end of the grounding wire to the transformer's secondary terminal S2 (or K2), and the other end to the grounding copper busbar of the terminal box or protection panel.

Check Grounding Continuity: Use a multimeter to measure the grounding loop resistance to ensure a reliable connection and the absence of loose connections or oxidation.

Identification and Protection: Hang a "Grounded" sign near the grounding point to prevent accidental disconnection.

IV. Special Scenario Handling:
Multiple CTs Forming Differential Protection: All secondary circuits should share a single grounding point within the protection panel to avoid unbalanced current caused by distributed grounding.

Shielded Cable Handling: The shielding layer of the secondary cable should be grounded at both ends in the switchyard and control room to suppress electromagnetic interference. However, this does not affect the single-point grounding requirement of the secondary winding itself.

Grounding Guarantee During Temporary Work: During live-line work, if it is necessary to disconnect the secondary circuit, a temporary grounding point must be established first. The grounding point must be restored after the work is completed.

⚠️ Special Reminder: Always disconnect the power or take equipotential bonding measures before operation. It is strictly forbidden to disconnect the secondary circuit of a running CT without short-circuiting.