How to prevent current transformer insulating oil deterioration?
Aug 27, 2025| I. Operating Environment Control
1. Temperature Management
Avoid long-term overload operation of the transformer and maintain the top oil temperature at ≤85°C (at an ambient temperature of 40°C).
Regularly inspect the cooling system to ensure the radiator is unobstructed and the fan is operating properly.
2. Moisture-Proof Sealing
Inspect the transformer gaskets, junction box, and other parts, and replace any worn seals to prevent moisture intrusion.
Keep the silicone sealant dry (replace if discoloration exceeds 2/3).
II. Oil Maintenance
1. Regular Testing
Perform insulation oil testing at least annually, including:
Dissipation Factor (tanδ ≤ 4%)
Breakdown Voltage (≥ 35 kV)
Water Content (≤ 35 ppm)
2 Oil Treatment and Replacement
Minimally degraded oil should be treated to acceptable standards using a vacuum oil filter.
Severely degraded oil (tanδ > 4% or water content > 35 ppm) requires complete replacement.
III. Operating Specifications
1. Oil Filling Process
When replacing or replenishing oil, vacuum filling should be used to prevent air intrusion.
New oil must be vacuum degassed and dehydrated (water content ≤ 20 ppm) before injection.
2. Abnormality Handling
Immediately shut down and investigate any abnormalities in the oil chromatographic analysis (e.g., excessive acetylene or hydrogen).
IV. Preventive Measures
Strengthen relay protection to reduce sudden oil temperature rises caused by short-circuit faults.
Transformers that have been out of service for more than six months must have their oil quality retested before re-operation.