How to regularly check whether the error of the current transformer changes over time?

Oct 16, 2024|

1. Establish a regular inspection plan:
According to the use environment and importance of the current transformer, formulate a reasonable inspection cycle. Generally speaking, for current transformers used as standards and with special requirements by users, the inspection cycle is two years; for current transformers used for general measurement, the inspection cycle can be determined to be two to four years based on their technical performance, environmental conditions and frequency of use.
For current transformers of level 0.2 and above, if the error change exceeds 1/3 of its allowable error during the inspection cycle, the inspection cycle should be shortened by half.
2. Choose a suitable inspection method:
Comparison method:
Self-inspection circuit: When the rated transformation ratio of the transformer to be inspected is 1, the self-inspection circuit can be used for inspection. Connect the primary winding and secondary winding of the transformer to be inspected, and judge whether the error of the transformer is within the allowable range by measuring the ratio of the output current of the secondary winding to the input current of the primary winding.
Comparison circuit: Generally, the comparison circuit is used for inspection. Compare the transformer under test with a standard transformer of known accuracy level, and calculate the error of the transformer under test by measuring the difference in the output current of the two transformers. The standard should be two levels higher than the transformer under test. If there is no standard with two levels higher, a standard with one level higher than the transformer under test can also be used as the standard, but the error of the transformer under test should include the error value of the standard.
Comparison circuit for symmetrical branch grounding: When the accuracy level of the current transformer used by the instrument under test is 0.1 or above, and the rated primary current is small (for example, less than 1A), the primary circuit should be indirectly grounded through a symmetrical branch or other methods. First, put the switch in the appropriate position, adjust the resistance and capacitance until the indication of the high-impedance millivoltmeter is the minimum, and the L1 terminal is close to the ground potential.
Difference method:
Difference method principle to measure the current output error of non-traditional current transformers: Use the difference method principle to measure the current output error of non-traditional current transformers. The error measuring device in the figure is a current ratio meter type. The galvanometer is connected in parallel to the differential current loop. When the current micro-difference source is adjusted to make the galvanometer indicate balance, the current in the differential current loop is close to zero.
The difference method principle is used to measure the voltage output error circuit of non-traditional current transformers: the circuit of measuring the voltage output error of non-traditional current transformers using the difference method principle measurement device. The error measuring device is an AC potential difference type. The galvanometer is connected in series to the differential voltage loop. When the voltage micro-difference source is adjusted to make the galvanometer indicate balance, the current in the differential voltage loop is close to zero. S is a low-inductance shunt with an accuracy of not less than 0.02. The secondary current of the current standard device is converted into a voltage with the same nominal value as the secondary output of the tested transformer, and then the error is measured according to the impedance bridge principle.
3. Requirements for testing equipment:
Standards: Standard transformers or other current ratio standards used as calibrators must meet the following requirements:
Standards should be two accuracy levels higher than the transformer to be tested. If there is no standard with two higher accuracy levels, a standard with one higher accuracy level than the transformer to be tested can also be used as a standard, but the error of the transformer to be tested should be included in the error of the standard.
During the calibration cycle, the error change of the standard shall not exceed 1/3 of its allowable error.
Standards must have a valid calibration certificate. The difference between the secondary load during use and the load marked on the certificate shall not exceed ±10%.
Error measuring device: The measurement error caused by the measuring device shall not be greater than 1/10 of the allowable error of the transformer to be tested, of which the measurement error caused by the sensitivity of the device shall not be greater than 1/20, and the measurement error caused by the minimum scale value shall not be greater than 1/15.
Monitoring ammeter: The accuracy level of the monitoring ammeter shall not be lower than level 1.5, and the internal impedance of the ammeter shall remain unchanged in all indication ranges.
Current load box: When the ambient temperature is 23±5℃, at rated frequency, the current load box is within the range of 5%~120% of the rated current, and the operating error of the load box resistance and reactance shall not exceed ±3%.
Power supply and regulation equipment: The power supply and regulation equipment should have sufficient capacity and adjustment fineness, and should ensure that the power supply frequency is between 49.5~50.5Hz, and the waveform distortion factor shall not be greater than 5%.
4. Control of detection environment conditions:
The ambient temperature has a great influence on the error of the current transformer, so it should be tested within the specified temperature range. Generally speaking, the error of the current transformer should meet its error performance requirements at an ambient temperature of -25℃~55℃.
The humidity of the detection environment should also be controlled within a certain range to avoid the influence of humidity on the equipment.
The detection site should avoid the influence of interference sources such as strong magnetic fields and electric fields to ensure the accuracy of the test results.
5. Data recording and analysis:
Each test should record in detail the model, specification, number, test time, test environment temperature, humidity and other information of the current transformer, as well as the error data obtained by the test, including ratio difference (ratio difference) and phase difference (angle difference).
Compare the test data of different periods to observe the trend of error changes. If the error gradually increases over time and exceeds the allowable error range, the cause should be analyzed and corresponding measures should be taken, such as repairing, replacing or adjusting the use conditions of the current transformer.
A curve showing the change of error over time can be drawn to more intuitively show the change of error. By analyzing the curve, it can be determined whether the change of error is regular and whether there are abnormal fluctuations.
6. Handling of abnormal situations:
If the error of the current transformer is found to exceed the allowable error range during the test process, the transformer should be stopped immediately and further inspection and analysis should be carried out.
Check whether the appearance of the current transformer is damaged, deformed, overheated, and other abnormal phenomena, as well as whether the connection is loose and the contact is poor.
Conduct insulation resistance test, DC resistance test, ratio test and other related tests on the current transformer to fully understand the performance of the transformer.
According to the inspection and test results, determine the cause of the error exceeding the standard and take appropriate measures to repair or deal with it. If it cannot be repaired, a new current transformer should be replaced.
After handling the abnormal situation, the current transformer should be re-tested to ensure that its error is within the allowable range before it can continue to be used.