Installation and use instructions for current transformers
Sep 05, 2022| (1) The installation of current transformers depends on the equipment and equipment, usually in the following categories:
①Install the current transformer on the metal material structure.
② In the area where the bus duct crosses the wall or concrete floor, fix the current transformer on the wall or concrete floor immediately with basic screws, or first make a rectangular frame structure of angle steel and bury it in the wall or concrete floor , and then fix the stainless steel plate (about 4mm thick) with the same size as the frame on the frame with screws or arc welding, and then fix the current transformer on the stainless steel plate. The current transformers are usually installed in places with a necessary aspect ratio from the road surface. Since the current transformers themselves are heavy during installation, care should be taken to avoid damage to the jade bottle when it is transported to the dead.
③ During installation, the management centers of the three current transformers should be on the same floor plan, the spacing of each voltage transformer should be the same, and finally the current transformer base should be well grounded.
(2) The primary winding resistance of the current transformer is connected in series with the measured line, and the second winding resistance is connected in series with the electrical measuring instrument. The optical rotation mark cannot be wrongly selected during wiring. In the specific work, because of the standard limitation, it is also possible to select one current transformer for each phase and complete reverse connection of the terminal buttons again, which is all possible.
(3) In the three-phase circuit, the transformation ratio and volume of the current transformers of each phase should be the same.
(4) The winding of the current transformer again cannot lead the way. Otherwise, it will cause high working voltage, which will seriously endanger the safety of machinery, equipment and operating staff; in addition, due to the over-temperature of the transformer core, the voltage transformer will be burnt, and the deviation of the current transformer will also be enlarged to a certain extent. Therefore, when working on the secondary circuit, first short-circuit the current transformer side again.
(5) The secondary side end button of the current transformer needs to have a grounding device on one side, so as to avoid the thermal breakdown of the insulation layer on the secondary side, which will cause damage to personal safety and machinery and equipment (for 500V and the following current transformer secondary side grounding device is required).