Installation Specifications for Current Transformers
Apr 28, 2023| 1. The installation of the current transformer must be firm, and the metal exposed part of the transformer shell should be reliably grounded.
2. The same group of current transformers should be installed in the same direction to ensure that the positive directions of the primary and secondary circuit currents of the group of current transformers are consistent, and the nameplate can be easily observed as much as possible.
3. The secondary side of the current transformer is not allowed to be open circuited. When only one secondary circuit is used for the secondary double-circuit transformer, the other secondary circuit should be reliably shorted.
4. The secondary side of the low-voltage current transformer may not be grounded. Because the insulation grades of the wires, electric energy meters and transformers used in the low-voltage metering device are the same, the maximum voltage that can withstand is basically the same; in addition, after the secondary winding is grounded, the insulation level of the primary circuit of the whole device to the ground is reduced, which is easy to make the insulation weak point The energy meter or transformer is damaged when high voltage is applied (such as being struck by induction lightning). In order to reduce damage from lightning strikes, it is also better not to ground the secondary side.