Introduction to Installation Specifications of Electrical Current Transformer
Feb 18, 2022| ①The installation of the Electrical Current Transformer must be firm, and the metal exposed part of the transformer shell should be grounded reliably.
②The same group of Electrical Current Transformers should be installed in the same direction to ensure that the positive directions of the primary and secondary circuit currents of the group of Electrical Current Transformers are consistent, and the nameplate can be easily observed as much as possible.
③The secondary side of Electrical Current Transformer is not allowed to open circuit. When only one secondary circuit is used for the secondary double-round transformer, the other secondary circuit should be reliably short-circuited.
④ The secondary side of the low-voltage Electrical Current Transformer may not be grounded. Because the insulation grades of the wires, electric energy meters and transformers used in the low-voltage metering device are the same, the maximum voltages that can be tolerated are basically the same; in addition, after the secondary winding is grounded, the insulation level of the primary circuit of the whole set of devices to the ground is reduced, which is easy to cause insulation weaknesses. The electric energy meter or transformer is damaged when high voltage is applied (such as by inductive lightning strike). In order to reduce the damage from lightning strikes, it is also better to not ground the secondary side.