Precautions for using Zero Sequence Current Transformer
Mar 18, 2022| The polarity connection of Zero Sequence Current Transformer should be correct. Zero Sequence Current Transformer is generally marked with decreasing polarity. If the polarity connection is incorrect, it will affect the measurement, and even when multiple Zero Sequence Current Transformers are connected in parallel on the same line, all will cause a short circuit. accident.
The secondary circuit should be provided with a protective grounding point and connected reliably. In order to prevent the high voltage from entering the low voltage side after the insulation breakdown between the primary and secondary windings, endangering personal and instrument safety, a protective grounding point should be set on the secondary side of the Zero Sequence Current Transformer. Only one grounding point is allowed, which is generally close to Zero The box terminal of the Sequence Current Transformer is grounded.
The secondary winding is not allowed to open circuit during operation. Otherwise, it will lead to the following serious consequences: high voltage on the secondary side, endangering personal and instrument safety; overheating, possibly burning out the windings; increasing the measurement error.
The secondary circuit of the Zero Sequence Current Transformer used for electric energy measurement should not be connected to relay protection devices and automatic devices to prevent mutual influence.