Preventive Measures for Electrical Current Transformer Burning

Jun 01, 2021|

1 Electrical Current Transformer burned reason

(1) The Electrical Current Transformer is opened for the second time, which generates high voltage and burns out the Electrical Current Transformer.

(2) The electrical current transformer has been used for a long time, and the insulation is aging, and local breakdown or discharge occurs, resulting in overvoltage, causing the Electrical Current Transformer to heat and burn out.

(3) The electrical current transformer once connected to the aluminum row contact surface is too oxidized, the contact resistance is too large, and the heat causes the Electrical Current Transformer to burn out.

(4) The user has been overloaded for a long time, causing the Electrical Current Transformer to heat up and burn out.


2 There is a problem with the user's circuit breaker and wiring of the special transformer

(1) Generally, 10kV vacuum circuit breakers and SF6 circuit breakers are equipped with overcurrent and overload protection. The circuit breaker can trip correctly when there is a phase-to-phase short circuit and overload, and the overvoltage is removed by the installed zinc oxide arrester. The Electrical Current Transformer for high-voltage metering for special transformers under our jurisdiction is installed between the isolating switch and the circuit breaker, so that if there is a problem with the Electrical Current Transformer, neither the circuit breaker nor the arrester can remove the fault, and the upper-level circuit breaker will be tripped and removed. Failure to expand the scope of the power outage, and at the same time, the Electrical Current Transformer will burn out due to the delayed removal of the fault.

(2) When a single-phase grounding occurs on the user side, because the circuit breaker does not trip, it is necessary to pull the offline branches of a public line one by one in order to find the grounding point. This will also cause the public line to be disabled and increase the power outage range.

(3) The insulation of the lightning arrester on the user side is aging and cannot effectively prevent overvoltage.


3 Take countermeasures

(1) Install a watchdog circuit breaker to avoid branch faults and power outages of the entire feeder, especially to ensure that the branch circuit breaker can be reliably tripped when the power side is single-phase grounded.

(2) Connect the Electrical Current Transformer for measurement to the back of the circuit breaker to ensure that the circuit breaker and arrester operate correctly when the Electrical Current Transformer fails to remove the fault.

(3) Strengthen users' high-voltage metering Electrical Current Transformer and lightning arrester high-voltage insulation test (the regulations stipulate no more than 4 years), early detection of the insulation aging degree of the metering Electrical Current Transformer and arrester, timely replacement, to avoid the occurrence of a power outage caused by the burning of the metering Electrical Current Transformer.

(4) Regularly clean the user's equipment once to reduce pollution flashover and avoid insulation degradation.