Principles for the installation and selection of current transformers

Oct 11, 2023|

1. Primary side rated current
For the selected current transformer, the rated current on the primary side should be 1.0 to 1.3 times the load current during normal operation of the line.
2. Rated voltage
The selected current transformer should have a rated voltage of 0.5 kV or 0.66 kV.
3. Accuracy class
If it is used for measurement, a current transformer with an accuracy grade of 0.5 or 0.2 should be selected; if the load current changes greatly, or the load current is lower than 30% of the rated current of the primary side of the current transformer during normal operation, a current transformer with a grade of 0.5 should be selected. device.
4. Number of turns and ratio
When selecting a current transformer, the transformation ratio and the number of turns of the current transformer can be determined according to actual needs.
5. Model Specifications
After the transformation ratio is determined according to the primary load current of the power supply line, the model of the current transformer is determined according to the actual installation situation.
6. Rated Capacity
The secondary rated capacity of the current transformer should be greater than the actual secondary load, and the actual secondary load should be 25% to 100% of the secondary rated capacity. The capacity determines the load impedance of the secondary side, and the load impedance affects the accuracy of measurement or control. The load impedance is mainly affected by the resistance value of the measuring instrument and relay coil, reactance and wiring contact resistance value, and the resistance value of the secondary connecting wire.
In practical applications, if the overload protection device of the motor needs to be connected to the current transformer, the metering (control) device should be separated from the protection device, so as not to affect the reliability of the protection.