Problems that should be paid attention to in the operation of current transformer
Apr 25, 2022| 1. The secondary side of the current transformer should not be opened during operation. Once the secondary side is open, it will burn out due to excessive iron loss and high temperature, or the secondary winding voltage will rise and the insulation will be broken down, resulting in high-voltage electric shock. Danger. Therefore, when replacing the meter, such as exchanging the ammeter, active meter, reactive meter, etc., the current loop should be short-circuited first and then the metering meter should be exchanged. When the meter is adjusted, first connect it to the secondary circuit, then remove the shorting wire and check whether the meter is normal.
2. If the current transformer has a buzzing sound, check whether the inner iron core is loose, and tighten the iron core bolts.
3. One end of the secondary side of the current transformer and the outer casing should be reliably grounded.