Technical requirements for split core current transformers

Nov 11, 2019|

1. Rated capacity: Apparent power consumed when the rated secondary current passes through the secondary rated load. The rated capacity can be expressed in terms of apparent power V.A or by secondary rated load impedance Ω.

2. Primary rated current: The electrical load current allowed to pass through the primary winding of the split core current transformers . The current transformer used in the power system has a rated current of 5 to 25000 A, and the precision current transformer used for the test equipment is 0.1 to 50000 A. The current transformer can be operated for a long time at one rated current. When the load current exceeds the rated current value, it is called overload. When the current transformer runs for a long time, it will burn out the winding or reduce the service life.

3. Secondary rated current: It is allowed to pass the primary induced current of the secondary winding of the current transformer.

4. Rated current ratio (variable ratio): the ratio of primary rated current to secondary rated current.

5. Rated voltage: * Large voltage (effective value in kV) that the primary winding can withstand for a long time to the ground, should not be lower than the rated phase voltage of the connected line. The rated voltage of the current transformer is divided into several voltage levels of 0.5, 3, 6, 10, 35, 110, 220, 330, 500kV.

6, 10% multiple: Under the specified secondary load and any power factor, when the current error of the current transformer is -10%, the primary current is a multiple of its rated value. The 10% multiple is a technical indicator related to relay protection.

7. Accuracy level: indicates the level of the transformer's own error (ratio and angular difference). The accuracy level of the current transformer is divided into 0.001 to 1 various levels, and the accuracy is greatly improved compared with the original. The electrical instruments used in the power distribution control panels of power plants, substations, and power units are generally 0.5 or 0.2; the relay protection for equipment and lines is generally not less than 1; when used for electric energy measurement, The load capacity or the amount of electricity used is selected according to the requirements of the regulations (see **).

8. Ratio difference: The error of the split core current transformers  includes two parts: the ratio difference and the angle difference. The ratio error is abbreviated as the ratio difference, generally indicated by the symbol f, which is equal to the difference between the actual secondary current and the primary current converted to the secondary side, and the ratio of the primary current converted to the secondary side, expressed as a percentage.

9. Angle difference: The phase angle error is simply referred to as the angular difference, which is generally represented by the symbol δ, which is the phase difference between the secondary current vector and the primary current vector after the rotation of 180°. It is prescribed that the secondary current vector leads the primary current vector δ to be a positive value, and vice versa to a negative value, and the minute (') is used as a unit of calculation.

10. Thermal stability and dynamic stability multiple: When the power system is faulty, the current transformer is subjected to the thermal effect and electric power of the huge current caused by the short-circuit current. The current transformer should have the ability to withstand without being damaged. The capacity is expressed in terms of thermal stability and dynamic stability multiples. The thermal stability factor refers to the ratio of the current that does not cause the heat of the current transformer to exceed the allowable limit and the rated current of the current transformer within 1 s of the thermal stable current. The dynamic stability factor is the ratio of the *current current value to the current rating that the current transformer can withstand.