The treatment method when the secondary side of the current transformer is open circuit

Oct 06, 2023|

(1) Find out which group of current loops and open circuits of the current transformer the fault belongs to, and whether it will affect the relay protection device. Report to dispatch and exit protection that may cause malfunction.
(2) The primary load current should be reduced as much as possible. If the current transformer is seriously damaged, the load should be transferred in time for power outage inspection and treatment (try to change the operating mode so that the user does not have a power outage).
(3) The secondary side of the current transformer should be short-circuited at the nearest test terminal as soon as possible, and then the open circuit point should be checked and dealt with. When short-circuiting, good short-circuiting wires should be used and carried out according to the drawings. Wear insulating boots, insulating gloves, and use insulating tools.
(4) If sparks are generated during short circuit, it means the short circuit is effective. In the circuit behind the short contact point, the fault point can be further found.
(5) If no spark is generated during short circuit, the short circuit may be invalid. The fault point may be in the circuit before the short contact point. The short contact point can be changed forward point by point to narrow the inspection scope. In order to shorten the time of secondary side open circuit, it is best to short-circuit from the terminal block of the current transformer terminal box first.
(6) Within the scope of the fault, focus on checking terminals and components that are prone to failure, or parts that have been moved during maintenance and other work.
(7) After the fault is detected, if the fault can be handled by itself, such as loose external components such as terminals, poor contact, etc., it can be processed immediately, and then put into the exiting protection.
(8) If it is a fault that cannot be handled by itself (such as the current transformer, inside the relay) or a fault that cannot be found out by itself, it should be reported to the superior in time and relevant personnel should be sent to deal with it (the secondary side of the current transformer should be short-circuited first). Or change the operating mode to transfer the load, and perform power outage inspection and treatment (to prevent long-term loss of protection).