What is the reason for the old electrical current transformer burnt
Jul 26, 2023| The first reason is that the secondary side of the Electrical Current Transformer is caused by an open circuit due to weak wiring.
In the process of using the Electrical Current Transformer, if the secondary side is open due to the disconnection of the wiring, the current will be equal to zero, and the impedance will be infinite. We know that the Electrical Current Transformer is actually a step-up transformer, so it will be in A very high electromotive force is generated on the secondary coil, sometimes reaching a voltage of several thousand volts, which will increase the magnetic flux density of the Electrical Current Transformer and cause serious saturation of the iron core, which will cause the The iron core is overheated and burns out the Electrical Current Transformer, which is one of the common burning causes of the Electrical Current Transformer.
The second reason is because the overload running time is too long
If the Electrical Current Transformer is overloaded for a long time, the coil will heat up. If the time is long, the Electrical Current Transformer will be burned due to the overheating of the coil.
The third reason is - the burnout caused by the increase of the contact resistance on the secondary side
During the use of the Electrical Current Transformer, if the conductive material connected does not meet the requirements, this will cause the contact resistance of the wiring to be too large and generate heat. When the heat reaches a certain temperature, the Electrical Current Transformer will also burn out.