What safety precautions should be taken when wiring current transformers?

Dec 19, 2025|

1. Secondary side must be reliably grounded. All current transformers must have their secondary side S2 terminal grounded at a single point to prevent high voltage from the primary side from entering the secondary side and ensure personal safety. The grounding wire should be secure and reliable, and its resistance value should meet requirements.

2. Secondary side open circuit is strictly prohibited. The secondary side must remain closed during operation. An open circuit will generate dangerous voltages of several kilovolts, which may damage equipment and endanger safety. If it is necessary to disconnect the secondary circuit, the S1-S2 terminals must be short-circuited first.

3. Correct polarity connection. The primary side current must flow from P1 to P2. The secondary side S1 is connected to the current inflow terminal of the instrument/protection device, and S2 is grounded. Reversed polarity will cause measurement errors or protection malfunctions.

4. Conductor cross-sectional area requirements. The secondary circuit connection wires must use copper core insulated wires with a cross-sectional area of ​​not less than 4 mm² to ensure mechanical strength and measurement accuracy.

5. Other Precautions

The terminals must not be subjected to additional tensile force.
The load impedance of the secondary circuit must not exceed the specified value.
When multiple current transformers (CTs) are used for differential protection, the polarity of each CT must be consistent.