What tests should Power Current Transformer do?
Feb 15, 2023| When implementing the open-circuit method for demagnetization, select a winding with a smaller number of turns in the primary (or secondary) winding to pass 10% to 15% of the rated primary (or secondary) current. Decrease the current to zero smoothly and slowly. During the demagnetization process, the peak voltmeter connected to both ends of the winding with the largest number of turns should be monitored. When the indicated value reaches 2600v, demagnetization should be performed at this current value.
When implementing closed-circuit demagnetization, connect a resistor equivalent to 10 to 20 times the rated load on the secondary winding (considering sufficient capacity), pass power frequency current to the primary winding, increase from zero to 1.2 times the rated current, and then evenly slowly drops to zero.
If the core of the Power Current Transformer is wound with two or more secondary windings, one of the secondary windings is connected to the demagnetization resistor during demagnetization, and the remaining secondary windings are open.
Note: When measuring the error of the Power Current Transformer for metrology, select the appropriate standard device and measuring equipment according to the accuracy level and verification regulations of the Power Current Transformer to be tested.