Preventive Measures for Current Transformer Burning

Feb 17, 2023|

1 Causes of current transformer burnout

(1) The secondary open circuit of the current transformer generates high voltage and burns out the current transformer.

(2) The service life of the current transformer is too long, the insulation is aging, local breakdown or discharge occurs, and overvoltage is generated, which causes the current transformer to heat up and burn out.

(3) The contact surface of the current transformer once connected to the aluminum row is too heavily oxidized, the contact resistance is too large, and the heat causes the current transformer to burn out.

(4) The user is overloaded for a long time, causing the current transformer to heat up and burn out.

2 There are problems with the circuit breaker and wiring of the special transformer user

(1) Generally, 10kV vacuum circuit breakers and SF6 circuit breakers are equipped with overcurrent and overload protection. When there is a phase-to-phase short circuit or overload, the circuit breaker can trip correctly, and the overvoltage is cut off by the installed zinc oxide arrester. The current transformers for high-voltage metering of the dedicated substation users under our jurisdiction are all installed between the isolating switch and the circuit breaker, so that once the current transformer fails, neither the circuit breaker nor the lightning arrester can remove the fault, and the circuit breaker at the upper level will trip and remove it. fault, thereby expanding the scope of power outages, and at the same time, the current transformer will be burned due to the delay in removing the fault.

(2) When a single-phase grounding occurs on the user side, because the circuit breaker does not trip, it is necessary to pull the off-line branches of a common line one by one to find the grounding point, which will also cause the public line to be deactivated and increase the scope of power outages.

(3) The insulation of the surge arrester on the user side is aging and cannot effectively prevent overvoltage.

3 take countermeasures

(1) Install a watchdog circuit breaker to prevent branch faults from affecting the entire feeder power outage, especially to ensure that the branch circuit breaker can reliably trip when the power side is single-phase grounded.

(2) Connect the metering current transformer to the back of the circuit breaker to ensure that the circuit breaker and lightning arrester operate correctly to remove the fault when the metering current transformer fails.

(3) Strengthen the high-voltage insulation test of users' high-voltage metering current transformers and surge arresters (no more than 4 years according to regulations), early detection of the insulation aging degree of metering current transformers and surge arresters, and timely replacement to avoid power outages caused by burnout of metering current transformers.

(4) Regularly clean the user's primary equipment to reduce pollution flashover and avoid insulation degradation.