Why can't the secondary side of the current transformer be open?

Dec 28, 2022|

1. The original current is determined by the detection circuit. When the load resistance is different, the initial current is also different. In normal operation, the secondary pole of the current transformer is short-circuited equivalently, and the demagnetization effect of the current is very strong, that is to say, in the initial position, the magnetomotive force of the secondary pole is similar. As a result, the directions are reversed, so the required resultant magnetic potential and corresponding excitation current is small.

2. If the second side of the current transformer is disconnected, the original current will all become excitation current, increasing the magnetic flux of the iron core, the iron core will be oversaturated, and the iron consumption will increase sharply, causing the transformer to heat and damage. At the same time, the large number of turns in the secondary winding will induce dangerous high voltages, endangering the safety of operators and measuring equipment.