Dec 26, 2022| 1. The construction shall be carried out according to the drawings, the wiring of the lines shall be accurate, the number marks at both ends shall be clear, and the range of the labels shall meet the specified requirements.
the
2. The wire or cable of the secondary circuit shall be made of copper wire, the wire cross section of the current transformer circuit shall not be less than 2.5 square millimeters, and the wire cross section of the voltage transformer circuit shall not be less than 1.5 square millimeters.
the
3. The first end of the current transformer outlet should select a dedicated current terminal, and the secondary winding not used by the current transformer should be short-circuited and grounded on the wiring board.
the
4. There should be no joints in the box wires of the secondary circuit, and there should be no joints between control cables or cables. If joints are required, terminal boxes for transition connections shall be used.
the
5. The polarity of the current transformer cannot be reversed or phase sequence. Various designs and procedures are available. When the transformer uses differential protection, the current phasor diagram of the two arms must be measured before it can be put into operation to confirm whether the connection is correct.
the
6. The layout of the secondary circuit wires should be neat and beautiful. The connecting screws between the wires and electrical components and terminal blocks must not have false connections or loose connections, and the distance between wire clamps should meet the regulations.