Wiring and Fixing Principle of Miniature Current Transformer

May 09, 2022|

The wiring of the current transformer should follow the series principle: the primary winding should be connected in series with the circuit under test, and the secondary winding should be connected in series with all instrument loads.


2) Select an appropriate change according to the current to be measured, otherwise the error will increase. big. At the same time, the secondary side must be grounded to prevent damage to the insulation when the primary side is pressed into the secondary low voltage side, resulting in personal and equipment accidents.


3) It is absolutely not allowed to disconnect the secondary side, because once the circuit is disconnected, the primary current I1 will all become the excitation current, resulting in a sudden increase in φm and E2, resulting in excessive saturation magnetization of the iron core, which will cause the iron core to heat up and even burn out coil; at the same time, the magnetic circuit is oversaturated and magnetized, which increases the error. When the current transformer is working normally, the secondary side is approximately short-circuited. If it is suddenly turned on, the excitation electromotive force suddenly changes from a small value to a large value, and the magnetic flux in the iron core exhibits a severely saturated flat top. waveform, so when the magnetic flux crosses zero, the secondary winding will generate a very high vertex wave, the value of which can reach thousands or even tens of volts, which is great for the safety of crisis handlers and the insulation performance of the instrument Influence. Also, an open circuit on the secondary side can generate hundreds of volts from E2, which can cause an electric shock if touched. Therefore, the secondary side of the current transformer is provided with a short circuit switch to prevent the primary side from being disconnected. As shown in Figure 1, when K0 is in use, once the secondary side is disconnected, the circuit load should be removed immediately and then stopped. Once everything is processed it can be reused.


4) In order to meet the needs of measuring instruments, generators, transformers, sockets, busbar sectional circuit breakers, busbar circuit breakers, bypass circuit breakers and other circuits for relay protection, circuit breaker fault judgment and fault recording, etc., provide 2 to 8 secondary windings. For high-current grounding systems, it is usually based on three-phase configuration; for low-current grounding systems, it can be based on two-phase or three-phase configurations according to specific requirements.


5) When installing a protective current transformer, the protection of the primary protection device should be cancelled as much as possible. area to be set. For example, if there are two sets of current transformers and the location allows, they should be placed on either side of the circuit breaker so that the circuit breaker is within the cross protection range.


6) In order to prevent the busbar failure and busbar failure of the pillar-type current transformer housing, the current transformer is usually arranged on the output side or the transformer side of the circuit breaker.


7) In order to reduce the damage caused by the internal fault of the generator, a current transformer for automatic adjustment of the excitation device should be installed on the output side of the generator stator winding. To facilitate analysis and detect internal faults before the generator is incorporated into the system, a current transformer for measuring instruments should be installed at the neutral point of the generator.