Protection CTs have different characteristics than metering CT. Protection CTs have high saturation point as it has to continuously sense fault current even during fault also. These CTs have low accuracy & are classified as 5P10, 10P10 etc.

  • Product Introduction

Wuxi Liou Electronics Co.,Ltd is one of the leading manufacturers and suppliers of dual core protection & measuring current transformer in China. Our factory offer high quality customized products made in China with low price. Welcome to contact us for quotation.

 

Dual core protection & measuring current transformer


Defination:

Metering CT – High accuracy CTs are used for metering as they have low saturation point. CTs are available in following accuracy class – 0.1, 0.2, 0.5,1,3,5. These values indicate percentage error at the rated primary current. It means a CT of 50/5A with 0.1 accuracy will have a max error of 0.1 when 50A current passes through the primary.

Metering CTs are designed in such a way that CT is not damaged by high current during fault. During fault, CT gets saturated & output stays in the range of measuring instruments.

Protection CT – Protection CTs have different characteristics than metering CT. Protection CTs have high saturation point as it has to continuously sense fault current even during fault also. These CTs have low accuracy & are classified as 5P10, 10P10 etc.

Example – CT with class 10P10 – Where first letter 10P indicates the maximum(10%) percentage error & last number 10 indicates the number of times the rated current.

Dual Core CT– Such type of CT has two cores, it means CT has two secondary windings & one primary winding. Dual core CT can be used for two simultaneous applications like metering & relay protection.

202206050856260db2adefc5034e58939d7843444f8c47 (1)_wps

1. Dimensions ( unit: mm)

20220605091746fccb1b19158e45e29e0178955c1dbc41_wps


2.  Schematic diagram

20220605093337095cc6e4fbd3438699ccb85aa516da85_wps


3.  Electrical specifications

PART NUMBER

LO-CT-600D

TERMINAL MAKRING

1S1-1S2

2S1-2S2

Accuracy Class

0.5/FS10

10P20

Current Ratio

Primary Turns

Rated Capacity

 600/5

1

15VA

15VA


4.   Technical Requirements

S/N

Description

Electrical specifications

1

Hi-pot test P-S

AC3.0KV,1mA,60s No breakdown

2

Insulation resistance P-S

1000MΩMin @DC500V

3

Operation   temperature

-40 ºC -          +125 ºC

4

Storage   temperature

-40 ºC -          +85 ºC



Hot Tags: Dual Core Protection & Measuring Current Transformer, China, manufacturers, customized, quotation, low price, made in China, Hall Effect High Precision Current Sensor, Zero Sequence Fault Current Transformer, DC Residual Current Sensor, Short Circuit Protection Current Transformer, Residual Current Transformer, Protection Electrical Current Transformer Center