1: 1000 0.1 Class Current Transformer (NRC08)
The three-phase current transformer is also called the three-in-one transformer as the AC current signal acquisition component. Generally, it can be used with multi-loop current monitoring device
- Product Introduction

Introduciton
The Three Phase DC Immune Current Transformer (CT) is a cutting-edge device designed to measure three-phase alternating current (AC) while effectively rejecting any direct current (DC) and external magnetic interference. This capability makes it ideal for complex power systems where AC and DC coexist, such as renewable energy installations and industrial applications. By utilizing advanced materials and design techniques, the Three Phase DC Immune CT ensures precise current measurements, enhancing system efficiency and reliability. Its robust anti-magnetic features provide further protection against external disturbances, making it a critical component for accurate monitoring and control in demanding electrical environments.
Description
- 50/60 Hz,Three Phase,AC Current Sensor
- Dynamic Range from 5 to 100Amps
- Meets IEC 60044-1/IEC61869-2 Class 0.1/0.2
- Immune to external AC magnetic field. Immune to DC current & DC magnetic field
- Very low temperature coefficient
- Meets UL class B (130ºC) thermal insulation system
- Meets UL 94V-0
- AC isolation resistance: 4KV for 60s
- Resistant to DC component :≤±3%
|
ELECTRIC SPECIFICAITON AT 25℃ |
||||||||||
|
Model number |
Turns Ration |
Ipri4 |
Iout5 |
Iprimax6 |
Ioutmax7 |
Resistant to DC component |
Accuracy Class3 |
RL8 |
Magnetic shield |
Frequency range |
|
Amps |
mA |
Amps |
mA |
% |
|
Ohms |
Tesla |
(Hz) |
||
|
LO-ADC723DT |
1:2500 |
5 |
2 |
60 |
24 |
≤±3% |
0.1/0.2 |
5-20 |
300mT |
50-60 |
|
1:2000 |
5 |
2.5 |
60 |
30 |
||||||
|
1:2500 |
10 |
4 |
60 |
24 |
≤±3% |
|||||
|
1:2000 |
10 |
5 |
60 |
30 |
||||||
|
1:1000 |
10 |
10 |
60 |
60 |
No shield |
|||||
|
1:2500 |
5 |
2 |
80 |
32 |
≤±3% |
|||||
|
1:2500 |
10 |
4 |
80 |
32 |
||||||
|
1:2500 |
10 |
4 |
100 |
40 |
||||||
|
1:2500 |
20 |
8 |
100 |
40 |
||||||
Note:
1.Output voltage is proportional to the derivative(di/dt)of the input current based on the Rogowski Coil principle.
2.All current and voltages assumed to be sinusoidal waveforms at Fr, the constant rated frequency in Hz, measured as RMS value.
3.Accuracy class per IEC60044-1Table 11.
4.Ipri=Rated primary current.
5.Iout=Rated secondary current.
6.Iprimax=Sensed max primary current.
7.Loutmax=Sensed max secondary current.
8.RL=Terminating resistance. Varying terminating resistance increases or decreases output Voltage /Ampers according to following
equation RL=Vout*Nsec/Ipri
|
ABSOLUTE MAXIMUM RATINGS |
|
|
Operating free air temperature range |
-40ºC to 85ºC |
|
Storage temperature range |
-40ºC to 100ºC |
|
LEADS INFORMATION |
|
|
24AWG UL1569 Lead wires |
Leads length:L±5mm |
|
Stripped and tinned |
L1+1/-0mm |
Mechanical specificaiton

Wuxi Liou Electronics Co Ltd
We aim at the achievement of a richer mind and body and the living for 1: 1000 0.1 Class Current Transformer (NRC08). In recent years, we have achieved greatness in business image and sales volume and won the sound reputation in the trade owing our staff keep striving and pioneering. We are full of confidence in our products and hope to get your approval. We will develop together with you with the quality of our products and the reputation of our company.Hot Tags: three phase dc immune current transformer, China, manufacturers, customized, quotation, low price, made in China, Residual Current Transformer High Current factory, Zero Phase Current Transformer, Earth Fault Current Transformer, High Accuracy CT Digital Meter Current Sensor, Three Phase Current Transformer 1 3000, Wound Type Current Transformer