Current Transformer PCB Mounting CT Wide Linear Range 2500: 1

Current Transformer PCB Mounting CT Wide Linear Range 2500: 1

20-1000 Hz,Single Phase,AC Current Sensor ¨ Dynamic Range from 20 to 200Amps ¨ Very low temperature coefficient ¨ Meets UL class B (130ºC) thermal insulation system ¨ Meets UL 94V-0 ¨ AC isolation resistance: 4KV for 60s

  • Product Introduction
The quality of our Three Phase Current Transformer 1: 2000, Three Phase Current Transformer, Zero Sequence Ground Fault Current Transformer is guaranteed to meet the standards so that each product is shipped and used without harming the environment where we live together. Our purpose is '100% client fulfillment by our product high-quality, price tag &, our staff service' and enjoy a superb reputation amongst clientele. Our company has always insisted on creating developing roads with technology, establishing the market by quality, and has a complete and scientific quality management system. With the business philosophy of "professional technology, quality first, teamwork strategy, and common growth", our company strives to develop and continuously improve.

   

Mechanical Specification

General-Purpose-20A-200A-Input-20-2000Hz-Operation-Frequency-Current-Transformer-PCB-CT.webp (1)

Description
¨   20-1000 Hz,Single Phase,AC Current Sensor
¨   Dynamic Range from 20 to 200Amps
¨   Very low temperature coefficient
¨   Meets UL class B (130ºC) thermal insulation system
¨   Meets UL 94V-0
¨   AC isolation resistance: 4KV for 60s

Application
•   Digital electricity meter
•   Recording
•   Power monitoring
•   Energy management
•   Alternative energy monitoring

ELECTRIC SPECIFICAITON AT 25ºC(60Hz)


Model number

Turns Ration

Ir4

VmaxRMS5

Te6(typ)

Accuracy
Class3

DCR

Weight

Frequency
range




Amps

V


 @100%Load

Ohms

(g)

(Hz)


LO-GP0001

1:1000

20

7.0

1023

3

24


20-1000


LO-GP0002

1:2000

50

13.7

2046

3

106


20-1000


LO-GP0003

1:1000

50

11.6

1016

3

35


20-1000


LO-GP0004

1:1500

75

15.5

1520

3

80


20-1000


LO-GP0005

1:1000

100

16.5

1021

3

22


20-1000


LO-GP0006

1:2000

200

31.0

2037

3

73


20-1000


Note:
1.Output voltage is proportional to the derivative(di/dt)of the input current based on the Rogowski Coil principle.
2.All current and voltages assumed to be sinusoidal waveforms at Fr, the constant rated frequency in Hz, measured as RMS value.
3.Accuracy class per IEC60044-1Table 11.
4.Ir=Maximum  input current to be linearly sensed
5.VmaxRMS=Maximum voltage (saturation) CT will develop
6.Te=Effective turns ratio including losses

General-Purpose-20A-200A-Input-20-2000Hz-Operation-Frequency-Current-Transformer-PCB-CT.webp (2)


ABSOLUTE MAXIMUM RATINGS

Operating free air temperature range

-40ºC to 85ºC

Storage temperature range

-40ºC to 100ºC

SOLDERING INFORMATION

Peak wave solder temperature

300ºC for 10Seconds

Pin finish

Tin

General-Purpose-20A-200A-Input-20-2000Hz-Operation-Frequency-Current-Transformer-PCB-CT.webp (3)

1

23456QQ图片20200716135417_meitu_1

We will continue to provide the public with impeccable and incomparable Current Transformer PCB Mounting CT Wide Linear Range 2500: 1, and strive to meet consumer demand. In line with the principle of seeking common ground while reserving differences and win-win cooperation, we encourage colleagues to be inclusive when facing problems. Our company is customer-oriented, pays attention to the 'people-oriented' management philosophy, and strives to provide customers with safe and reliable products.

Hot Tags: current transformer pcb ct, China, manufacturers, customized, quotation, low price, made in China, Precision AC Current Transformer, Mini Split Core Current Transformers, Wound Type Current Transformer, DC Immune High Accuracy Current Transformer, CT Series Current Transformers, DC Immune Current Transformers

[[ProKeywords]]
Send Inquiry