Split Core Current Transformer CT 50A 60A

Split Core Current Transformer CT 50A 60A

A current transformer is an instrument transformer that is used with a measurement or protection device where the secondary current is proportional to the primary current

  • Product Introduction
We will constantly satisfy our respected customers with our good excellent, superior value and superior assistance due to we're additional experienced and far more hard-working and do it in cost-effective way for Clamp on AC current Transformer, High-range Current Transformers, Split Core Type Current Transformer. Our company will win your trust and support for us with excellent product quality, preferential product prices, after-sales service, and business reputation. We wholeheartedly welcome new and old businessmen to visit our company for on-site inspection, visit and guidance! 80% of our products exported to over the world. We'll work whole-heartedly to improve our solutions and services.

55

 

Description

  • 47-5000 Hz,Single Phase,AC Current Sensor
  • Rated up to 50A
  • Dynamic Range from 10 to 50Amps
  • Linearity ≤0.1 Phase error < 15'
  • Very low temperature coefficient
  • Meets UL class B (130℃) thermal insulation system
  • Meets UL 94V-0
  • AC isolation resistance: 3.75KV for 60s
  • High current density

 

Application

• Switching power supplies

• Motor controls

• Power monitoring

• Energy management

• Alternative energy monitoring

 

ELECTRIC SPECIFICAITON AT 25

Model number

Turns Ration

Ipri1

Iout2

E-T3

RS

Linearity

LS4

Weight

Frequency

range

Amps

mA

V-uS

Ohms(Max)

 

H(Min)

(g)

(Hz)

LO-HF4001

1:1200

50

42

3000

40

≤0.1

10

20

47-5K

 

 

 

 

 

 

 

Note:

1.Ipri=Rated primary current.

2.Iout=Rated secondary current.

3.E-T is at Bi-Polar Only

4.Ls=Secondary inductance

 

Terminating resistor options

Ipri(Amps)

Terminating Resistor

E0

10

80

0.667

20

40

0.667

50

16

0.667

 

E-T=(E0*1/f)/2(Bi-Polar Only) E0=IP*(Rb/Tr)

E0=Output V Ip=Pri.Current Tr=Turns Ratio f=frequency Rb=Term Res

 

ABSOLUTE MAXIMUM RATINGS

Operating free air temperature range

-40℃ to 85℃

Storage temperature range

-40℃ to 100℃

SOLDERING INFORMATION

Peak wave solder temperature

300℃ for 10Seconds

Pin finish

Tin

 

Mechanical Specifications:

 

LO-HF4001 DIMENSIONS

 

Schematic diagram:

 

88

 

Wuxi Liou Electronics Co Ltd

Mainly designing all kinds of Split Core Current Transformer CT 50A 60A of ordinary, middle and high grades. Through continuous improvement, our company has consolidated its position as an industry leader in terms of quality. We aim at 100% product qualification rate, 100% contract fulfillment rate, and 100% service satisfaction rate. Adhering to the concept of 'User's success is our achievement', we sincerely welcome friends from all walks of life to come and guide us.

Hot Tags: 50a current transformer, China, manufacturers, customized, quotation, low price, made in China, Split-core current transformer, Residual Current Transformer Current factory, Hall Effect Split Core Current Transducer, High Frequency Current Transforemr 1: 1000, Split Core Current Transformers, opening split core current transformer

[[ProKeywords]]