Split Core Current Transformer with 400A/5A (three phase)
Split core AC current sensors have different hole sizes and current ratings to suit any application. Split core models are perfect for retrofits. Output is fixed at the industry standard.
- Product Introduction
Introduction
Split core AC current sensors have different hole sizes and current ratings to suit any application. Split core models are perfect for retrofits. Output is fixed at the industry standard.
Features
• High accuracy at 10-130% of rated current
• AC isolation resistance: 3KV for 60s
• Swing open for ease of installation
• Double secured latches per side and keying holes
• Rigid housing case with UL® 94V-0 durable plastic
• Safety standard: IEC/EN60044-1
• Nominal phase angle error and
Nominal linearity error: Conform IEC61869-2
ConformIEC60044-1
•Max.operation voltage: AC600V
Specificaiton
Item | Specificaiton |
Inputs | |
Frequency range 50-60Hz | |
Accuracy range 10-130% of rated current | |
Outputs | |
output at rated current 2mA-200mA | |
Enviromental | |
Operaiton temperature range -10°C to +60°C (+14°F to +140°F) | |
Storage temperature range -20°C to +85°C (+4°F to +185°F) | |
Lead length 70 ft black/white twisted pair wire leads-22 AWG | |
Certifications RoHS | |
Mechanical Specificaitons

Part Number | Description | A | B | C | D | E | ΦF | Primary Rated | Weight |
g | |||||||||
LO-SP3010 | CT 1:3000, 0.5% accuracy | 40.5 | 24.6 | 22 | 26 | 14.5 | 10 | 5, 15, 30, 50, 75,80 | |
LO-SP3016 | CT 1:3000, 0.5% accuracy | 44 | 27 | 29 | 31 | 19 | 16 | 50, 70, 100, 120 | |
LO-SP3024 | CT 1:3000, 0.5% accuracy | 75 | 46 | 45 | 35 | 19.5 | 24 | 100, 150, 200, 300 | |
LO-SP3036 | CT 1:3000, 0.5% accuracy | 91.6 | 58 | 57.4 | 40.9 | 22.8 | 36 | 300, 400, 500, 600 |
Installation

Application
● Data logging ● Recording ● Power monitoring | ● Energy management ● Alternative energy monitoring |
Our deep understanding of product application, and continuous improvement of technology make our Split Core Current Transformer with 400A/5A (three phase) has the ability to upgrade in a timely manner. We have a professional international trade team. Establishing and cultivating the core competitive advantage of an enterprise is an important strategic measure for us to gain a foothold and expand market share in the increasingly fierce market competition.Hot Tags: single phase split core ct, China, manufacturers, customized, quotation, low price, made in China, opening split core current transformer, Closed Loop Hall Effect Sensors, Clamp On Current Transformer, Split Core Hall Effect Current Sensor, DC Immune Current Transducer 1 2000, Core Balance Current Transformer