High Precision 1:2000 Current Transformer 5A-2.5mA PCB Mount
Current transformers are used in transformer-rated energy meters to measure the total power consumed and the current measure flow. Transformer-rated energy meters are different from self-contained energy meters used within homes as the electric energy involved is very low. When the current involved is more than 200 Amperes, as with most industries and factories, transformer-rated meters with current transformers are required.
- Product Introduction
Wuxi Liou Electronics Co.,Ltd is one of the leading manufacturers and suppliers of high precision 1:2000 current transformer 5a-2.5ma pcb mount in China. Our factory offer high quality customized products made in China with low price. Welcome to contact us for quotation.

Description
50/60 Hz,Single Phase,AC Current Sensor
Dynamic Range from 0.1 to 15Amps
Meets IEC62053-21 class 1
Meets IEC 60044-1 class 0.1 Phase error < 5'
Immune to external AC magnetic field. Immune to DC current & DC magnetic field
Very low temperature coefficient
Meets UL class B (130℃) thermal insulation system
Meets UL 94V-0
AC isolation resistance: 4KV for 60s
Application
• Electricity meter
• Recording
• Power monitoring
• Energy management
• Alternative energy monitoring
|
ELECTRIC SPECIFICAITON AT 25℃ |
||||||||||
|
Model number |
Turns Ration |
Ipri4 |
Iout5 |
Iprimax6 |
Ioutmax7 |
RS |
Accuracy Class3 |
RL8 |
Weight |
Frequency range |
|
Amps |
mA |
Amps |
mA |
Ohms |
|
Ohms |
(g) |
(Hz) |
||
|
LO-EM0004 |
1:2000 |
5 |
2.5 |
15 |
7.5 |
160MAX |
0.1 |
20 |
20 |
50-60 |
Note:
1.Output voltage is proportional to the derivative(di/dt)of the input current based on the Rogowski Coil principle.
2.All current and voltages assumed to be sinusoidal waveforms at Fr, the constant rated frequency in Hz, measured as RMS value.
3.Accuracy class per IEC60044-1Table 11.
4.Ipri=Rated primary current.
5.Iout=Rated secondary current.
6.Iprimax=Sensed max primary current.
7.Loutmax=Sensed max secondary current.
8.RL=Terminating resistance. Varying terminating resistance increases or decreases output Voltage /Ampers according to following
equation RL=Vout*Nsec/Ipri
|
ABSOLUTE MAXIMUM RATINGS |
|
|
Operating free air temperature range |
-40℃ to 85℃ |
|
Storage temperature range |
-40℃ to 125℃ |
|
SOLDERING INFORMATION |
|
|
Peak wave solder temperature |
300℃ for 10Seconds |
|
Pin finish |
Tin |

Dimensions:

Note: Pin1 & 3 are in phase. Primary: 1-2 Secondary: 3-4
Wuxi Liou Electronics Co Ltd
Hot Tags: high precision 1:2000 current transformer 5a-2.5ma pcb mount, China, manufacturers, customized, quotation, low price, made in China, Sensor Current Sensor Transformer, Electricity Meter Current Transformer, Current Transformer For Energy Meter, Class 0 1 High Accuracy Transformer, High Voltage Current Transformer, Low Voltage Transformer