High Precision current Transformer with primary bus bar
DC immune current sense transformers are used for sensing the AC currents where DC offsets also exist. The current sense transformers create a voltage when current flows. They are primarily made for sensing AC currents in a circuit so having a DC bias can distort the AC measurement. Some specialized alloys of magnetic materials are referenced as DC immune. DC immune means that they will not react or distort the AC measurement so there can be more accurate AC measurements even if there is a DC offset present.
- Product Introduction
Wuxi Liou Electronics Co.,Ltd is one of the leading manufacturers and suppliers of high precision current transformer with primary bus bar in China. Our factory offer high quality customized products made in China with low price. Welcome to contact us for quotation.


Description
¨ 50/60 Hz,Single Phase,AC Current Sensor
¨ Dynamic Range from 0.5 to 120Amps
¨ Meets IEC62053-21 class 1
¨ Meets IEC 60044-1 class 0.1 Phase error < 5'
¨ Immune to external AC magnetic field. Immune to DC current & DC magnetic field
¨ Very low temperature coefficient
¨ Meets UL class B (130℃) thermal insulation system
¨ Meets UL 94V-0
¨AC isolation resistance: 4KV for 60s
Application
• Electricity meter
• Recording
• Power monitoring
• Energy management
• Alternative energy monitoring
ELECTRIC SPECIFICAITON AT 25℃ | ||||||||||
Model number | Turns Ration | Ipri4 | Iout5 | Iprimax6 | Ioutmax7 | RS | Accuracy Class3 | RL8 | Weight | Frequency range |
Amps | mA | Amps | mA | Ohms | Ohms | (g) | (Hz) | |||
LO-ADC0001 | 1:2500 | 10 | 4 | 120 | 50 | 0.1 | 25 | 50-60 | ||
Note:
1.Output voltage is proportional to the derivative(di/dt)of the input current based on the Rogowski Coil principle.
2.All current and voltages assumed to be sinusoidal waveforms at Fr, the constant rated frequency in Hz, measured as RMS value.
3.Accuracy class per IEC60044-1Table 11.
4.Ipri=Rated primary current.
5.Iout=Rated secondary current.
6.Iprimax=Sensed max primary current.
7.Loutmax=Sensed max secondary current.
8.RL=Terminating resistance. Varying terminating resistance increases or decreases output Voltage /Ampers according to following
equation RL=Vout*Nsec/Ipri
Schematic diagram:

Dimensions:

Hot Tags: High Precision current Transformer with primary bus bar, China, manufacturers, customized, quotation, low price, made in China, Electricity Meter Current Transformer, Class 0 1 High Accuracy Transformer, High Voltage Current Transformer, Current Transformer For Energy Meter, Sensor Current Sensor Transformer, Low Voltage Transformer