Common Errors in Current Transformer Compensation
Jan 26, 2026| I. Errors in Compensation Calculation
Turns Compensation: Calculating a -0.5% ratio difference as -1% may lead to excessive secondary current, increasing the error.
Capacitor Compensation: Using a 50Ω capacitor with a 10Ω secondary impedance will reduce the effectiveness of phase difference compensation.
II. Errors in Operation Procedures
Secondary Side Open Circuit: Failure to ground during compensation or short-circuiting when replacing the meter may cause high-voltage hazards.
Wiring Errors: Reversing the polarity of P1-S1 will worsen both the ratio difference and phase difference.
III. Errors in Method Selection
Protective Transformer Compensation: Using turns compensation for 5P/10P transformers may lower the accuracy limit factor.
Magnetic Shaft Compensation: Relying solely on this may result in unbalanced ratio difference and phase difference compensation.
IV. Neglecting Process and Environmental Factors
Core Assembly: Insufficient precision will increase leakage flux.
Environmental Interference: Changes in temperature and humidity may cause error fluctuations.