What are the precautions for current transformer compensation?
Jan 23, 2026| I. Accurate Compensation Calculation
Turnings Compensation: The number of compensation turns must be accurately calculated based on the actual ratio difference to avoid over- or under-compensation. For example, if the ratio difference is -0.5%, but the compensation turns are calculated as -1%, it may cause excessive secondary current, increasing the error.
Capacitor Compensation: The capacitor value must be adjusted according to the secondary load impedance to ensure effective phase difference compensation. For example, if the secondary impedance is 10Ω, using a 50Ω capacitor may not effectively offset the phase difference.
II. Strictly Prevent Secondary Side Open Circuit During Operation
Safety Risk: An open circuit on the secondary side can lead to high-voltage hazards; reliable grounding must be ensured.
Operating Procedure: When replacing instruments, the secondary winding must be short-circuited to avoid open circuits.
III. Compensation Method Selection
Turnings Compensation: Only effective for ratio difference; phase difference requires separate handling.
Capacitor Compensation: Good for phase difference compensation, but a phase-shifting circuit is required when the secondary impedance is close to 0.
Magnetic shunt compensation: This must be combined with turns compensation to avoid uneven compensation due to ratio difference and angle difference.
IV. Process and Environment
Core assembly: Core assembly accuracy must be controlled to avoid increased leakage flux.
Environmental interference: Temperature, humidity, and electromagnetic interference must be controlled during testing.
V. Verification and Adjustment
Based on the calibration report: Adjust compensation measures according to the error data in the factory inspection report.
Recalibration: Recalibration is required after compensation to ensure the error returns to within the limits.