Correct construction method when installing Zero Sequence Current Transformer

Jun 10, 2022|

1. Ensure that the inner diameter of the Zero Sequence Current Transformer is larger than the outer diameter of the cable terminal;


2. Try not to dismantle the Zero Sequence Current Transformer during construction. If it must be dismantled, it must be restored to its original state after the work is completed;


3. The grounding wire must be made of stranded copper wire or tinned copper braided wire. The cross-section of the grounding wire should not be less than 25 mm2. The grounding end should be welded with terminals, and the relative position of the grounding wire and the zero-sequence current transformer should be properly handled. The ground wire must be installed on the ground copper bar;


4. The zero-sequence protection system must be set before power-on to ensure that the protection works normally.