Detection and treatment measures for common faults of current transformers

Oct 02, 2023|

1. What to do if there is abnormal sound or the iron core is overheated. During the operation of the current transformer, if problems such as an open circuit or overload in the secondary circuit occur, abnormal sounds or serious overheating of the iron core will occur. If the semiconductor paint surface is not evenly painted, it is easy to produce a loud sound. Therefore, if there are abnormal sounds or iron core overheating during the operation of the current transformer, it is necessary to observe the actual conditions of the side instruments in detail to find out the cause of the fault in time. If the abnormality of the current transformer is caused by a large load, the load needs to be appropriately reduced to ensure that it can meet the rated load requirements. In addition, the specific operation of the current transformer must be continued to be observed; if the abnormality of the current transformer is caused by the secondary circuit , stop the operation of the equipment immediately; if insulation damage causes discharge problems, the current transformer needs to be replaced in time.
2. Handling of abnormal operation. During the operation of the current transformer, problems such as open circuit and heating may occur, and problems such as loose bolts and strange sounds may occur. At this time, the staff need to take scientific and effective measures to deal with these problems, such as judging the current transformer. When the secondary circuit is open, it is necessary to comprehensively consider the meter indication, sound, etc.; when detecting the heating of the current transformer, it can be tested through the temperature test wax sheet. Especially when checking for an open circuit in the secondary circuit, if there is a problem, the indication of the ammeter will be "0", and the energy meter will be in a stopped state at this time, and then there will be a buzzing sound. At this time, there will be an abnormality in the current transformer. sound, which in turn scorches a large number of terminal strips. Once any of the above situations occurs during the operation of the current transformer, the operation of the equipment needs to be stopped immediately.
3. Secondary circuit open circuit processing. During the operation of the current transformer, high voltage on the secondary side may occur due to saturation of the magnetic flux in the iron core, causing discharge to occur at the open point of the secondary circuit, resulting in discharge sound or discharge sparks. In addition, the loss of the iron core will increase due to magnetic flux saturation and heat will be generated. In this case, odor and abnormal sound will be generated in the insulating material. At the same time, abnormal rotation speed of the electric energy meter is generally caused by the ammeter connected to the secondary side of the current transformer having no indication or the indication swinging. Therefore, once an open circuit occurs on the secondary side of the current transformer during the operation of the transformer, it is necessary to stop the operation of the equipment in time and take effective measures to deal with it. Once there is no way to carry out a power outage, the primary load current needs to be reduced as soon as possible, and the secondary circuit of the current transformer is connected in front of the open circuit point through an insulating tool to form a short circuit. After the fault is eliminated, the short circuit is removed.
4. Ensure that the primary terminal lead connector has good contact. Regularly check the contact condition of the terminal lead joints once a day to ensure that the contact area is sufficient, and to avoid overheating faults. It is necessary to make the equipotential connection between the expander cover and the L2 terminal to avoid potential floating. At the same time, the anti-rotation measures are applied to the lead-out of the secondary wire to avoid twisting of the internal lead wire due to external operations.
5. Make sure the test value is normal. When the measured dielectric loss factor tg value is abnormal during the operation of the current transformer, a comprehensive analysis of the relationship between tg, temperature and voltage is required; when tg shows obvious temperature changes with the increase of the test voltage, the operation needs to be stopped in time. If the chromatographic analysis results are abnormal, it is necessary to examine the growth trend, track and analyze the specific data, find out the reasons in time, and take effective measures.
6. Current transformer demagnetization inspection. Remanence in the transformer core may cause a sudden drop in current. For example, under large current conditions, the current transformer will cut off the secondary winding and the power supply will suddenly open circuit. When the residual magnetism exists in the transformer core, the magnetic permeability of the core will decrease, which will have a certain impact on the performance of the transformer. Transformers that have been used for a long time need to be demagnetized.