How to choose zero-sequence miniature current transformer
Aug 08, 2022| First of all, it is about zero-sequence miniature current transformers for small current line selection devices. For the small current line selection device, it has no set value, so the sequence current is only a criterion of the device, which requires our zero-sequence miniature current transformer to meet the threshold value of the device when the ground current is relatively small. When grounding, when using non-metallic grounding, the zero-sequence current transformer must also have a certain output, so as to meet the threshold value of the device.
For the small current line selection device, its own load impedance is actually very small, but each zero-sequence miniature current transformer should be connected to our device through a cable, so that the impedance of our cable becomes the main factor of our current transformer. load impedance. The load impedance of this zero-sequence current transformer is usually about 2.5Ω.
Regarding the above-mentioned, in fact, according to our past experience, we can also judge that the zero-sequence miniature current transformer is matched with the small current line selection device, and is suitable for variable ratio 150≤5 capacity: 5VA, or variable ratio: 40≤1 Capacity: 2.5VA.
Here, we should also point out that for the above two zero-sequence miniature current transformers, when the load impedance is 2.5Ω, the first time is 1A, and the second output is about 20 mA, if the zero-sequence miniature current transformer is 40A , the second unit can also be greater than or equal to 1A, because this transformation ratio relationship is not a stricter requirement.