Main technical requirements for miniature current transformers
Aug 10, 2022| 1 Additional volume: the apparent power consumed when the additional secondary current passes through the secondary additional load. The additional volume can be described by the apparent power V.A, and can also be described by the secondary additional load characteristic impedance Ω.
2. Primary additional current: the load current of electricity consumption that passes through the primary winding of the current transformer. The primary additional current of the current transformer used for the power supply system is 5 to 25000A, and the detailed current transformer used for the experimental equipment is 0.1 to 50000A. The current transformer can run for a long time under an additional current. When the load current exceeds the additional current value, it is called overload. The long-term overload operation of the current transformer will burn the winding or reduce the service life.
3 Secondary additional current: The primary magnetically induced current passing through the secondary winding of the current transformer.
4. Additional current ratio (transformation ratio): The ratio of primary additional current to secondary additional current is .
5. Additional working voltage: The larger working voltage that can be accepted by the primary winding for a long time to the ground (effective value is in kV), which should be higher than the additional phase voltage of the connected line. The additional working voltage of the current transformer is divided into 0.5, 3, 6, 10, 35, 110, 220, 330, 500kV and other rated voltages.
6 10% multiple: Under the specific secondary load and random power factor, when the current error of the current transformer is -10%, the multiple of the primary current to its additional value. The 10% multiple is the professional skill index value related to the relay protection device.
7 Accuracy level: Indicate the level of error (ratio difference and angle difference) of the voltage transformer itself. The accuracy level of the current transformer is divided into various levels from 0.001 to 1, which is greatly improved from the original accuracy. The surface of the electrical equipment in the control panel of the power distribution equipment of power stations, distribution stations, and electricity-consuming enterprises is generally selected as grade 0.5 or 0.2; the relay protection devices used for machinery equipment and routes are generally higher than grade 1; When measuring and verifying electromagnetic energy, the volume or power consumption of the load to be measured should be selected according to the technical specifications (see the first lecture).
8. Ratio difference: The error of the voltage transformer includes two parts: the ratio difference and the angle difference. The ratio error is generally called the ratio difference, which is generally described by the mark f, which is equivalent to the error between the specific secondary current and the primary current converted to the secondary side, and the ratio of the primary current converted to the secondary side, expressed in percentage.
9. Angle difference: The phase angle error is generally called the angle difference, which is generally described by the mark δ, which is the phase difference between the secondary current vector and the primary current vector after rotating 180°. If the standard secondary current vector is ahead of the primary current vector δ, it is coincident, and on the contrary, it is a negative number. Use points (‘) to measure the enterprise.
10 Thermal reliability and dynamic reliability multiples: When the power engineering system is abnormal, the current transformer is subject to the thermoelectric effect and electric driving force effect of the extremely large current caused by the short-circuit fault current. The current transformer should have the ability to accept and not be damaged. Yes, this kind of acceptance can be explained by thermal and dynamic multiples. The thermal reliability multiple refers to the ratio of the current that does not cause the current transformer to overheat to exceed the agreed limit and the additional current of the current transformer within 1s of the thermal reliability current. The dynamic reliability multiple is the ratio of the additional current between the instantaneous value of the larger current that the current transformer can accept.