How to determine if a current transformer needs compensation?

Jan 16, 2026|

I. Does the error exceed the limit?

Ratio difference (current error): If the actual ratio difference exceeds the limit specified for the accuracy class (e.g., for a 0.5 class transformer, the ratio difference must be within ±0.5%), compensation is required.

Phase difference (angle error): If the phase difference is too large (e.g., for a 0.5 class transformer, the phase difference must be ≤30′), compensation should also be considered.

II. Are the error characteristics abnormal?

Negative ratio difference: The ratio difference of an uncompensated current transformer is usually negative. If the negative value is too large, compensation is required.

Positive phase difference: The phase difference of an uncompensated current transformer is usually positive. If the positive value is too large, compensation is also required.

III. Is the application scenario sensitive?

High-precision measurement: In applications requiring high-precision measurement (e.g., metrology, scientific research), even if the error does not exceed the limit, compensation may be necessary to improve accuracy.

Protection Devices: In protection devices, excessive errors may affect the accuracy of protection actions, therefore compensation is required.

IV. Selection of Compensation Methods

Turnings Compensation: This method compensates for ratio differences by reducing the number of turns in the secondary winding. It is suitable for ratio difference compensation.

Capacitor Compensation: A capacitor is connected in parallel across the secondary winding. It provides positive compensation for ratio differences and negative compensation for angle differences. It is suitable for angle difference compensation.

Auxiliary Core Compensation: This method compensates for both ratio and angle differences using an auxiliary core, but the manufacturing process is more complex.

V. Practical Operation Suggestions

Review Inspection Report: Determine whether compensation is needed based on the error data in the inspection report provided with the current transformer at the factory.

Calculate Compensation Amount: If compensation is required, the compensation amount can be calculated based on the error data. For example, the turns compensation amount Δf = Nx/(N²-Nx) × 100%.

Adjust Compensation Measures: Adjust the compensation measures based on the calculation results. For example, increase or decrease the number of compensation turns, adjust the size of the compensation capacitor, etc.