What are the methods for compensating errors in current transformers?

Jan 14, 2026|

I. Magnetomotive Force Compensation

1. Turns Compensation

Principle: Reducing the number of turns in the secondary winding increases the secondary current, compensating for the ratio difference.

Formula: Compensation amount Δf = Nx/(N²-Nx) × 100%.

Applicable Scenarios: Suitable for ratio difference compensation, but care should be taken not to over-compensate, otherwise it may be counterproductive.

2. Parallel Impedance Compensation of Secondary Winding

Principle: Connecting a capacitor in parallel with the secondary winding generates a capacitive current magnetomotive force, compensating for ratio and phase differences.

Characteristics: The compensation effect is directly proportional to the secondary load impedance and capacitance.

II. Electromotive Force Compensation

1. Magnetic Shunt Compensation

Principle: Adding a magnetic shunt core outside the iron core reduces the cross-sectional area of ​​the auxiliary core, compensating for ratio and phase differences.

Characteristics: The compensation effect is significant at low currents.

2. Magnetic Shunt Short-Circuit Turn Compensation

Principle: Adding short-circuit turns to the magnetic shunt increases the magnetic shunt loss angle, compensating for phase difference.

Features: While smoothing the ratio difference curve, it also smooths the phase difference curve more effectively.

III. Other Compensation Methods

1. Auxiliary Core Compensation

Principle: Compensating for ratio and phase difference using an auxiliary core.

Features: Complex manufacturing process, but comprehensive compensation effect.

2. Capacitor Compensation

Principle: Connecting a capacitor in parallel across the secondary winding provides positive compensation for ratio difference and negative compensation for phase difference.

Features: In miniature precision current transformers, the capacitor compensation effect is relatively small when the secondary impedance is close to 0.

IV. Precautions

Turnings Compensation: The number of compensation turns should not be excessive, otherwise it may be counterproductive.

Capacitor Compensation: When the secondary impedance is close to 0, a phase-shifting circuit needs to be added to solve the phase difference problem.

Magnetic shunt compensation: Compensation for the magnetic shunt needs to be considered, and the cross-sectional area of ​​the auxiliary iron core should be reduced accordingly.

How to determine if a Hall sensor is damaged?