What are the methods for compensating errors in current transformers?
Jan 14, 2026| I. Magnetomotive Force Compensation
1. Turns Compensation
Principle: Reducing the number of turns in the secondary winding increases the secondary current, compensating for the ratio difference.
Formula: Compensation amount Δf = Nx/(N²-Nx) × 100%.
Applicable Scenarios: Suitable for ratio difference compensation, but care should be taken not to over-compensate, otherwise it may be counterproductive.
2. Parallel Impedance Compensation of Secondary Winding
Principle: Connecting a capacitor in parallel with the secondary winding generates a capacitive current magnetomotive force, compensating for ratio and phase differences.
Characteristics: The compensation effect is directly proportional to the secondary load impedance and capacitance.
II. Electromotive Force Compensation
1. Magnetic Shunt Compensation
Principle: Adding a magnetic shunt core outside the iron core reduces the cross-sectional area of the auxiliary core, compensating for ratio and phase differences.
Characteristics: The compensation effect is significant at low currents.
2. Magnetic Shunt Short-Circuit Turn Compensation
Principle: Adding short-circuit turns to the magnetic shunt increases the magnetic shunt loss angle, compensating for phase difference.
Features: While smoothing the ratio difference curve, it also smooths the phase difference curve more effectively.
III. Other Compensation Methods
1. Auxiliary Core Compensation
Principle: Compensating for ratio and phase difference using an auxiliary core.
Features: Complex manufacturing process, but comprehensive compensation effect.
2. Capacitor Compensation
Principle: Connecting a capacitor in parallel across the secondary winding provides positive compensation for ratio difference and negative compensation for phase difference.
Features: In miniature precision current transformers, the capacitor compensation effect is relatively small when the secondary impedance is close to 0.
IV. Precautions
Turnings Compensation: The number of compensation turns should not be excessive, otherwise it may be counterproductive.
Capacitor Compensation: When the secondary impedance is close to 0, a phase-shifting circuit needs to be added to solve the phase difference problem.
Magnetic shunt compensation: Compensation for the magnetic shunt needs to be considered, and the cross-sectional area of the auxiliary iron core should be reduced accordingly.