How to Ensure No Open Circuit on the Secondary Side of an Open-Type Current Transformer
Aug 03, 2026| I. Preliminary Design and Selection Protection
1. No fuses, air switches, or other easily disconnectable components should be installed in the secondary circuit to avoid the risk of open circuits at the source.
2. Use copper core cables with a cross-sectional area ≥ 2.5mm² for secondary connection wires to prevent wire aging and breakage.
3. Use dedicated test terminals in the secondary circuit to maintain continuous circuit continuity during testing and disassembly.
II. Core Installation and Operation Specifications
1. Strictly follow the sequence of connecting the secondary wires first, then closing the transformer core opening, maintaining a closed secondary circuit throughout.
2. Before disassembling or assembling secondary instruments, the secondary winding terminals must be reliably short-circuited using a dedicated short-circuit clip; short-circuiting with ordinary wire is prohibited.
3. Use insulated tools throughout the operation, stand on an insulated mat, and never work on the circuit between the transformer and the short-circuit point.
III. Idle and Maintenance Management
1. For transformers not currently in use, the secondary winding terminals must be short-circuited and grounded to eliminate the risk of open circuits.
2. During secondary circuit switching operations, a short-circuit prevention measure should be adopted before switching to avoid circuit disconnection during operation.
3. Regular inspections should be conducted, focusing on checking for loose terminals and aging or damaged wires, and addressing any potential loose connections promptly.
IV. Redundant Protection Configuration
1. A secondary-side open-circuit alarm or voltage limiter can be installed to provide rapid warning and clamp overvoltage in case of abnormalities.
2. Only one reliable grounding point should be set on the secondary side to avoid abnormal circuit disconnection caused by multiple grounding points.