How to install and regulate current transformers

Jun 23, 2023|

1. The metal frame where the current transformer is selected to be installed (such as the busbar frame in the power distribution cabinet) must be firm, and the metal exposed part of the transformer shell must be reliably grounded.

2. Correct wiring according to the diagram in the manual, the number marks at both ends of the wires should be clear, and the range of marks should meet the requirements of the rules.
3. The same group of current transformers should be installed in the same direction to ensure that the positive direction of the primary and secondary circuit currents of the current transformer group is the same, and it is as easy as possible to observe the nameplate.

4. The secondary side of the current transformer is not allowed to open circuit. When the secondary round transformer only uses one secondary circuit, the other secondary circuit should be reliably shorted.

5. Copper wire should be used for the secondary circuit conductor or cable. The cross section of the current transformer line conductor should not be less than 2.5mm2, and the cross section of the voltage transformer circuit conductor should not be less than 1.5mm2.

6. The first row at the outlet of the current transformer should select a dedicated current terminal, and the secondary winding not used by the current transformer should be short-circuited and grounded on the terminal board.

7. There should be no joints for the secondary circuit conductors in the disk and the cabinet, and there should be no joints between the control cables or conductors. If splices are necessary, higher strength terminals should be used for transition connections.
8. The polarity of the current transformer cannot be reversed, and the phase difference and phase difference should meet the requirements of design and regulations. For the transformer wiring of differential protection, the double-arm current phasor diagram must be measured before putting into operation to check the correctness of the wiring.

9. The wires of the secondary circuit should be arranged neatly and beautifully. The connecting screws between the wires and electrical components and terminal blocks must not be loose. The distance between the wires and the clamping point should meet the requirements of this rule.

10. The insulation of the secondary circuit to the ground should be good, and the voltage circuit and the current circuit should not be mixed.

11. The current and voltage circuits should be grounded at the outlet of the secondary side of the transformer. (Note: The secondary side of the low-voltage current transformer cannot be grounded. Since the insulation grades of the wires, watt-hour meters and transformers used for the low-voltage metering device are the same, the maximum voltage that can be tolerated is basically the same; when the other secondary windings are grounded, the entire device's The insulation level of the primary circuit is reduced, and it is easy to damage the insulation weakness of the energy meter or transformer (such as being struck by induction lightning). In order to reduce the damage caused by lightning strikes, it is best not to ground the secondary side.)

12. The current transformer should be installed in a complete power distribution cabinet. This kind of current transformer is not installed on the body, and finally check whether the installation and wiring are correct.